Service Menu - GE Digital Energy LP 11 Operating Manual

Uninterruptible power supply 3-5-6-8-10 kva
Table of Contents

Advertisement

OUTPUT OFF
NO INPUT POWER
PROG. SHUTDOWN
WITHIN 0:09:17
PROG. SHUTDOWN
LEFT 0:14:03
SHUTDOWN
ALARM (PRESS UP)
IMMEDIATE
SHUTDOWN

5.3.3 Service menu

When the default screen is displayed you can enter the first service screen by pressing the keys 'Down' (2) and
'Enter/Reset' (3) simultaneously for approx. 1 second. Using the 'Up' (4) and 'Down' (2) keys you can scroll
through several service screens.
SERVICE SCREENS
ENTER
exit
SERIAL NUMBER
l051/01 0020A0307A
SOFTWARE VERSION
R1.0; 640777
FAN SPEED
10
INV.DC: + 375
HEATSI.TEMP:
0
TRANSF.TEMP: 310
FLOAT CHARGE:
1
OUTPUT FAST :
0
TSTAMP
Q4
6028773
1
FREQ RANGE:
2%
NO LOAD
:
1
QUICK BATTERY
TEST PRESS ENTER
OPM_LPE_11X_3K0_10K_1GB_V041
The output is switched off due to a faulty situation, indicated by the second
line.
The output will be switched off via the RS232 interface. The second line
indicates the time until shutdown.
The output is switched off by a remote command (RS232/SNMP). The second
line indicates the time until wake-up.
The output is switched off by the 'no-load shutdown' feature: no input voltage
and no load. If the input voltage is restored, the output will be available again.
The wire on connector J3 pin 3-4 (rear panel, plug-in card 12) is interrupted.
The output is no longer available. To restart the unit, restore the connection
and turn the on/off switch (rear panel, 7) off and on again.
The intro service screen. 'Enter/Reset' returns to the default screen.
The serial number of the UPS.
Release number of the installed software and production code of the UPS.
Service information about fan speed (min. 10, max. 30) and internal DC
voltage.
Service information on internal temperature levels, values in mV over the
temperature sensors.
Upper line: '1' = batteries have reached float voltage.
Second line: service information on output converter.
Service information on internal timer.
Frequency tracking range: output converter frequency will follow the bypass
frequency within these limits before returning to its own internal frequency.
Standard setting: nominal ±2%. Can be changed into nominal ±4% or ±6%.
See 5.3.4 Set-up Menu.
No-load shutdown: after a 10 minutes delay the UPS will shut down during
utility failure if the load is < 2%. It will restart after the mains returns or when
the unit is switched off and on again.
Default setting = 1 (active). For disabling this feature see 5.3.4.
Start of the manual Quick Battery Test.
See for more information section 5.4.2 'Quick battery test'