Section 1 - General Information; Unpacking/Inspection; Protection Systems; System Set Led - Generac Power Systems GUARDIAN 04758-0 Installation And Owner's Manual

Air-cooled automatic standby generators
Table of Contents

Advertisement

DANGER
Only qualified electricians or contractors should
!
attempt such installations, which must comply
strictly with applicable codes, standards and
regulations.
1.1

UNPACKING/INSPECTION

After unpacking, carefully inspect the contents
for damage.
• This standby generator set has been factory sup-
plied with a weather protective enclosure that is
intended for outdoor installation only.
If this generator is used to power electrical load
circuits normally powered by a utility power
source, you are required by code to install a
transfer switch. The transfer switch must effec-
tively isolate the electrical system from the util-
ity distribution system when the generator is
operating (NEC 700, 701 and 702). Failure to
isolate an electrical system by such means will
result in damage to the generator and also may
result in injury or death to utility power work-
ers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix his or her signature under the
consignor's memo of loss or damage.
If you note loss or damage after delivery, separate the
damaged materials and contact the carrier for claim
procedures.
"Concealed damage" is understood to mean damage
to the contents of a package that is not in evidence at
the time of delivery, but is discovered later.
4
Section 1 — General Information
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
1.2

PROTECTION SYSTEMS

Unlike an automobile engine, the generator may have
to run for long periods of time with no operator pres-
ent to monitor engine conditions. For that reason, the
engine is equipped with the following systems that
protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
There are LED readouts on the control panel to noti-
fy you that one of these faults has occurred. There is
also a "System Set" LED that is described below.
1.3

SYSTEM SET LED

The "System Set" LED is lit when all of the following
conditions are true:
1. The Auto/Off/Manual switch is set to the AUTO
position.
2. The utility voltage being supplied to the unit is
being sensed by the Control PCB. If the utility
sense voltage is not connected to the unit or if it
is below 168 volts AC, then the system set light
will flash rapidly. This indicates that if the
Auto/Off/Manual switch is placed in the Auto posi-
tion , the generator will start.
3. The "Not In Auto" dip switch is set to the OFF
position on the control board.
4. No alarms are present, for example, low oil pres-
sure, high temperature, etc.
3. Overcrank
4. Overspeed

Advertisement

Table of Contents
loading

Table of Contents