Specifications; Fuel Consumption; Reconfiguring The Fuel System - Generac Power Systems Quietsource 004917-2 Owner's Manual

Liquid-cooled, prepackaged standby generator
Table of Contents

Advertisement

1.10 SPECIFICATIONS

1.10.1 GENERATOR SPECIFICATIONS
Model
Rated Max. Cont.
AC Power Output (kW)
Rated voltage (volts)
No. of Rotor Poles
Driven Speed of Rotor
Rotor Excitation System Direct excited brush type
Type of Stator
Rotor/Stator Insulation
1.10.2 ENGINE SPECIFICATIONS
Make ......................................................................................Ford
Displacement ..................................................................3.0 liters
Cylinder Arrangement ..............................................................V-6
Valve Arrangement ..............................................Overhead Valve
Firing Order ................................................................1-4-2-5-3-6
Number of Main Bearings............................................................4
Compression Ratio............................................................9.3 to 1
No. of Teeth on Flywheel ........................................................164
Ignition Timing at 1800 rpm..............................30 degrees BTDC
Spark Plug Gap ..................................................0.035-0.045 inch
Recommended Spark Plugs
Motor Craft..........................................................AG, SF 32PGM
Oil Pressure....................................................................40-50 psi
Crankcase Oil Capacity........................5.0 U.S. quarts (4.7 liters)
Recommended Engine Oil..........................................SAE 5W-20
Type of Cooling System ..................Pressurized, closed recovery
Cooling Fan ..............................................................Pusher Type
Cooling System Capacity..................3.0 U.S. gallons (11.4 liters)
Recommended Coolant ............................Use a 50-50 mixture of

1.11 FUEL CONSUMPTION

Natural Gas:
% of Load
25%
m
3
/hr
3.1
ft
3
/hr
110.3
LP Vapor:
% of Load
25%
m
3
/hr
1.3
ft
/hr
45.6
3
QUIETSOURCE™ Liquid-cooled 30 kW Generators
Single-phase
4917-0
27 (NG), 30 (LP)
120/240
4
1800
4 Wire
Class F/H
ethylene glycol base
and de-ionized water.
50%
75%
100%
5.9
8.5
11.0
209.0
299.5
387.0
50%
75%
100%
2.4
3.5
4.5
86.4
123.8
160.0
Section 1 — General Information
Fuel consumption is given at rated maximum con-
tinuous power output when using natural gas rated
at 1000 Btu per cubic foot. LP gas is rated at 2520
Btu per cubic foot. Actual fuel consumption
obtained may vary depending on such variables as
applied load, ambient temperature, engine condi-
tions and other environmental factors.
Fuel pressure for a natural gas set up should be five
inches to 14 inches of water column (0.18 to 0.5
psi) at all load ranges.
Fuel pressure for an LP vapor set up should be 11
inches to 14 inches of water column (0.4 to 0.5
psi) at all load ranges.
1.12 RECONFIGURING THE FUEL
SYSTEM
All models are configured for natural gas from the
factory.
To reconfigure the fuel system from NG to LP vapor,
follow these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet
port (Port 1) of the demand regulator (Figure 1.8).
3. Remove the brass hose fitting from the outlet port
(Port 1) of the demand regulator.
4. Remove pipe plug from Port 2.
5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure
and type for configuration.
10. Reverse the procedure to convert back to natural
gas.
Figure 1.8 — Reconfigure the Fuel System
Port 1
PLUG
HOUSING
PORTS
NG FUEL SYSTEM
Generac
NOTE:
NOTE:
Port 2
FUEL HOSE
FUEL HOSE
BRASS HOSE
BRASS HOSE
FITTING
FITTING
OUT
OUT
PORT 1
PORT 2
HOUSING
PORTS
LP FUEL SYSTEM
®
Power Systems, Inc.
PLUG
7