WARNING:
WARNING:
WARNING:
WARNING:
WARNING:
The engine's exhaust contains harmful
emissions. ALWAYS have adequate
ventilation when operating . Direct exhaust
away from nearby personnel.
BEFORE STARTING
Generator and Control Panel
CAUTION:
NEVER! manually start the engine with the
main, GFCI or auailliary circuit breakers in
the "ON" (closed) position.
1. Be sure and place the main, G.F.C.I. and aux. circuit
breakers (Figure 44) in the "OFF" position prior to starting
the engine.
Figure 44. Main, Aux. and GFCI
2. Connect the load to the UVWO terminals or auxiliary
receptacles as shown in Figure 45. These load
connection points can be found on the output terminal
panel. To gain access to the UVWO terminals or other
power receptacles, unlock the access cover and lift the
door.
The UVWO terminals are protected by a plastic cover,
remove this cover to gain access to the terminals.
Tighten terminal nuts securely to prevent load wires from
slipping out.
DCA-45SSIU2 — OPERATION AND PARTS MANUAL (STD) — REV. #7 (06/13/07) — PAGE 41
DCA-45SSIU2 — GENERATOR START-UP PROCEDURE
Circuit Breakers
Figure 45. Load Connections
3. Close all engine enclosure doors (Figure 46).
Figure 46. Engine Enclosure Doors
4. Place the voltage selector switch in the desired voltage
position (Figure 47).
Figure 47. Voltage Selector Switch