LENNOX HEARTH PRODUCTS • CRESTLINE™ SERIES B-VENT GAS FIREPLACES • 36"/42" LSBV MODELS • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel #
Minimum
5.0" WC
Natural Gas
(1.24 kPa)
11.0" WC
Propane
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel #
Low
Natural
(Lo) 2.2" WC
Gas
(0.55 kPa)
(Lo) 6.3" WC
Propane
(1.57 kPa)
Table 3
Test gauge connections areprovidedonthefront
of the millivolt gas control valves (identified OUT
forthemanifoldsideandINforinletpressureside.
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the
gas supply piping system by closing its
equipment shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psi
(3.5 kPa).
4
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters)abovesealevelusingthestandardburner
orifice sizes (marked with an "*" in Table 4). For
elevations above 4500 feet, contact your gas
Maximum
supplier or qualified service technician.
10.5" WC
(2.62 kPa)
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
13.0" WC
by either:
(3.24 kPa)
• Using gas that has been derated by the gas
company.
• By changing the burner orifice to a smaller
size as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition or,
High
in Canada, the CAN/CGA-B149.1 codes - latest
(Hi) 3.5" WC
edition.
(0.87 kPa)
Install the appliance according to the regulations
(Hi) 10.0" WC
of the local authorities having jurisdiction and,
(2.49 kPa)
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or, in Canada,
the CAN/CGA-B149.1 - latest edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude.
In Canada - CAN/CGA-2.17-M91 (R2009) (high
altitude): THE CONVERSION SHALL BE CAR-
RIED OUT BY A MANUFACTURER'S AUTHO-
RIZED REPRESENTATIVE, IN ACCORDANCE
WITH THE REQUIREMENTS OF THE MANU-
FACTURER, PROVINCIAL OR TERRITORIAL
AUTHORITIES HAVING JURISDICTION AND
IN ACCORDANCE WITH THE REQUIREMENTS
OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
0-4500
(0-1372)
Table 4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Natural
Propane
Gas
Gas
drill size (inches)
drill size (inches)
#26 (0.147")
*
#45 (0.082")
*
H5805 •
39L66 •
* Standard size installed at factory
• Part /Cat. Number
Gas Valve Diagrams
See Figure 1 for Millivolt models and Figure 2
For Electronic Models.
Inlet Pressure Tap
Manifold Pressure Tap
Piezo
Igniter
Main Gas Control Knob
OFF/PILOT/ON
Figure 1 - - SIT Millivolt Gas Valve
Figure 2 - SIT Electronic Gas Valve
REQUIREMENTS FOR THE COMMON-
WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The flexible gas line connector used shall not
exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a
T-handle type valve.