Appendix A - Termination Locations
A = clearance to the termination frame above grade, veranda, porch, deck,
or balcony [16 inches (41 cm) minimum]
B = clearance to door, or sides and top of window, that may be opened [16
inches (41 cm) minimum for appliances ≤100 000 BTU/H (30kW)]
C = clearance to bottom of window that may be opened horizontally [36
inches (92 cm) minimum for appliances ≤100 000 BTU/H (30kW)]
D = no clearance to permanently closed window when installed with ap-
proved glass penetration termination
E = clearance to permanently closed window [16 inches 41 cm recom-
mended to prevent condensation on window]
F = vertical clearance to ventilated soffit located above the termination
within a horizontal distance of 2 feet (61 cm) from the centreline of the
termination [22 inches (56 cm) minimum]
G = clearance to unventilated soffit
[16inches (41 cm) minimum to non-combustibles]
[22 inches (56 cm) minimum to combustibles]
H = clearance to outside corner [9 inches (23 cm) minimum]
I =
clearance to inside corner [12 inches (31 cm) minimum]
J = * not to be installed above a meter/regulator assembly within
40" (103 cm) horizontally from the centreline of the regulator
K = clearance to service regulator vent outlet [3 feet minimum in the United
States] [*6 feet (1.8 m) minimum in Canada]
L = clearance to nonmechanical air supply inlet to building or the combus-
tion air inlet to any other appliance [16 inches (41 cm) minimum for
appliances ≤100 000 BTU/H (30kW)]
M = clearance to mechanical air supply inlet
both dwellings
only permitted if veranda, porch, deck, or balcony has an open side
that is equal to or greater than the depth of the enclosed area
*
as specified in CGA B149 Installation Codes. Note: local Codes or
Regulations may require different clearances
Part No. XG0123
[*6 feet (1.8 m) minimum]
N =
clearance above paved sidewalk or a paved driveway located on
public property [*7 feet (2.1 m) minimum]
P = clearance under veranda, porch, deck, or balcony
[16 inches (41 cm) minimum
[22 inches (56 cm) minimum
Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighbouring buildings
[18 inches (46 cm) minimum]
S = clearance from corner in recessed location
[12 inches (31 cm) minimum]
T = maximum depth in recessed location
[48 inches (122 cm) minimum]
U = minimum width for back wall of recessed location
[24 inches (61 cm) minimum]
V = no horizontal clearance between the frames of two terminations that
are level.
W = horizontal clearance between the frames of two terminations that are
not level. [36 inches (92 cm) minimum]
a vent shall not terminate directly above a sidewalk or paved drive-
way which is located between two single family dwellings and serves
ME38-ODV-2 Homefire
to non-combustibles]
to combustibles]