Honeywell HE220 Installation Manual & Owner's Manual page 4

Humidifier and installation kit
Table of Contents

Advertisement

Available languages

Available languages

HE220, HE260 HUMIDIFIER AND INSTALLATION KIT
Determining Best Location for Humidifier
CAUTION
Temperature and Static Pressure Hazard.
Can cause property or equipment damage.
Locate humidifier where ambient temperature is between 32°F (0°C) and
160°F (71°C).
Do not install humidifier where freezing temperatures could occur.
Be sure supply plenum static pressure is no greater than 0.4 in. wc and water
pressure is no greater than 124 psi.
• Select a location for the humidifier on the supply (warm air stream) plenum. See
Fig. 1.
• Select a location that cannot damage the air conditioner A-coil during installation.
• Do not locate the humidifier on the furnace body.
• Allow adequate clearance in front of and above the humidifier so you can easily
remove the cover to perform routine maintenance.
— Mount the humidifier at least 3 in. (78 mm) above the furnace body to allow
adequate space for the solenoid valve and drain line.
— Mount the humidifier in a conditioned space to prevent freezing.
R E
Selecting Water Supply Location
• Use either hard or soft water in the humidifier and either hot or cold water. The
water flow rate, with the humidifier running, is 3.5 gal/hr (13 liters/hr) to flush the pad
and provide moisture for evaporation.
69-2630ES—03
H O
R N
T U
R N
T U
R E
W B
L O
Fig. 1. Typical humidifier installation locations.
T A L
O N
R I Z
R N
T U
R E
W N
D O
O
F L
O Y
4
R N
T U
R E
O Y
H B
H I G
M12808A

Advertisement

Table of Contents
loading

This manual is also suitable for:

He260

Table of Contents