g
UPS Type
ENCLOSURE
Sheet steel cubicle
Colour front
Colour cabinet
Protection
Dimensions (hxwxd, mm)
Dimensions (hxwxd, inch)
(height with castors)
Weight (with batteries, Kg)
Weight (with batteries, Lbs)
GENERAL DESIGN CRITERIA
Mechanical
Humidity
Safety
Surge capability
EMC
ENVIRONMENT
Ambient temperature
Audible noise at 1 meter
LX: OPM_LPU_11U_5K0_10K_1US_V030
:
5-11U
6-11U
:
VSD2
VSD2
:
RAL 9006 (aluminum)
:
RAL 9010 (white)
:
IP 20
:
680x313x730
680x313x730
:
26.8x12.3x28.7 26.8x12.3x28.7
:
134 kg
134 kg
:
295 Lbs
295 Lbs
:
IP20
:
95% non condensing
:
UL 1778; 2001, C-UL
EN 50091-1-1: 1999; EN 60950 / IEC 950: 2001
:
6kV 1.2/50µs; 3kA 8/20µs
:
FCC part 15, class A; EN 50091-2
:
-10 to +40°C (14 to 104°F)
:
40 - 50dB(A),
the audible noise is load and temperature dependent
42
Digital Energy
8-11U
VSD2
680x313x730
26.8x12.3x28.7
26.8x12.3x28.7
175 kg
386 Lbs
GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
LP Series
10-11U
VSD2
680x313x730
186 kg
410 Lbs