4.1 Transport

NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading
capacity. Move the UPS in its original package to the final destination room. Do not stack other
package on top.

4.2 Unpacking

Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to
the pallet. Remove the UPS from the pallet.
BE CAREFUL!
from the pallet! Never try to lift the unit by yourself!
The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate
measures to avoid damage on vulnerable floors.

4.3 Package Contents

The shipping box contains a LP-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.5.3) a
safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel
Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and
one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the
carrier and place of purchase immediately.

4.4 Location

Please refer to section 1.3 of 'IMPORTANT SAFETY INSTRUCTIONS'.

4.5 Installation

IMPORTANT
:
Before making any connection and switching on the LP UPS, please check the following conditions:
The voltage and frequency of your utility supply is 120/208/230/240 Vac and 50 or 60 Hz; from the
factory the input and output of the UPS are set to 208 Vac / 60 Hz.
Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the
UPS, as well as at the I/O terminals.
Overcurrent protection for the AC circuit is to be provided by others.
CAUTION:
UPS model
Operating input voltage
LP 5-11U
LP 5-11U /120V
LP 6-11U
LP 6-11U /120V
LP 8-11U
LP 10-11U
Table 1. external input fuse value
LX: OPM_LPU_11U_5K0_10K_1US_V030
4 - Installation
Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS
To reduce risk of fire, connect only to a circuit input/output provided with
branch circuit overcurrent protection in accordance with the National
Electrical Code, ANSI / NFPA 70, as indicated below:
Input overcurrent protection
(Amps)
120V
208V
35
60
40
70
60
70
9
Digital Energy
Output overcurrent protection
(Max. Amps)
240V
120V
120V
(1 X)
(2X)
30
40
20
40
20
35
50
25
50
25
45
70
35
60
80
40
GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
LP Series
208V
240V
25
20
25
20
30
25
30
25
40
35
50
40