For LP 8/10kVA:
8.
Remove all links between the terminals.
9.
Split both the load wires and spread one wire over
terminal 1-2 and the other over 3-4 respectively.
10. Connect the ground wire to terminal 5. Ground
connection is essential! See figure 15a.
11. Return to either 4.5.1.1 step 5 or 4.5.1.2 step 5
Figure 15a. Output cable splitting for

4.5.4 Input/output voltages: Software modification.

NOTE:
following this procedure you realize that the values shown in the LCD match the actual
input/output voltages.
1.
Switch on the circuit breakers 'utility' (8) and 'bypass' (9) (see also section 5.2, step 1-2)
2.
Go to the set-up menu. See 5.3.4 'Set-up Menu'
SETUP SCREENS
ENTER/RESET exit
3.
Using the push-buttons 'up' and 'down' you can scroll through the several set-up screens. 'Enter/Reset'
confirms the screen choice. Go to the set-up screen 'INPUT VOLTAGE'.
INPUT VOLTAGE
208V
4.
Here you can change the input voltage to 240 Volt. The value of the input voltage blinks. Scroll through its
settings by using the push-buttons 'up' and 'down', the new setting is confirmed by pressing 'Enter/Reset'.
INPUT VOLTAGE
240V
CHANGE TO
5.
Go to the set-up screen 'OUTPUT VOLTAGE'.
OUTPUT VOLTAGE
208V
6.
Here you can change the output voltage to 240 Volt. The value of the input voltage blinks. Scroll through
its settings by using the push-buttons 'up' and 'down', the new setting is confirmed by pressing
'Enter/Reset'.
INPUT VOLTAGE
CHANGE TO
240V
7.
To return to the default screen scroll to the set-up screens first and press 'Enter/Reset'. You can also wait
20 seconds: the time-out period of no key activity.
8.
You can now proceed with 5.1 or 5.2.