1. System Configuration

1.4 I/O expansion

The I/O points on the T1-16 and T1-28 are not expandable. The T1-40 and T1-40S,
however, provides I/O expandability by using the option cards, expansion rack and
expansion unit.
The T1-40/T1-40S can hold up to two option cards. Also, the T1-40/T1-40S can be
connected to either one expansion rack (2-slot or 4-slot) or one expansion unit. By
using the expansion rack, most of the T2 Series I/O modules can be used with the
T1-40/T1-40S.
· Available option cards
· Available expansion racks
· Available expansion units
· Available I/O expansion configuration
20
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
DI116: 16 points DC input
DO116: 16 points DC output
DD116: 8 points DC input + 8 points DC output
AD121: 1 channel analog input (0 to 5V or 0 to 20mA)
AD131: 1 channel analog input (-10 to +10V)
DA121: 1 channel analog output (0 to 20mA)
DA131: 1 channel analog output (-10 to +10V)
FR112: TOSLINE-F10 remote station
BU152: Up to 2 I/O modules can be mounted
BU154: Up to 4 I/O modules can be mounted
T1-EDR32: 16 points DC input + 16 points relay output
T1-EAR32: 16 points AC input + 16 points relay output
Model
Unit configuration
T1-16
T1-16
T1-28
T1-28
T1-40
T1-40(S)
or
T1-40S
T1-40(S)
+
T1-40(S)
+
T1-40(S)
+
+
T1-40(S)
+
T1-40(S)
DI116
DD116
DO116
DI116
+
DI116
DI116
+
DD116
6F3B0250
I/O points
16 points (8 in / 8 out)
28 points (14 in / 14 out)
40 points (24 in / 16 out)
56 points (40 in / 16 out)
56 points (32 in / 24 out)
56 points (24 in / 32 out)
72 points (56 in / 16 out)
72 points (48 in / 24 out)