Jenn-Air 30" (76.2 CM) Installation Instructions Manual page 12

30" (76.2 cm), 36" (91.4 cm) and 48" (121.9 cm) commercial style dual fuel convection ranges
Table of Contents

Advertisement

Available languages

Available languages

4-wire connection: Power supply cord
Use this method for:
New branch-circuit installations (1996 NEC)
Mobile homes
Recreational vehicles
In an area where local codes prohibit grounding through the
neutral
1. Remove the ground-link screw from the range frame. Save
the ground-link screw. Bend the ground link away from the
range so that it does not contact the range.
A
A. Ground-link screw
B. Ground link bent away from range
2. Connect the green ground wire from the power supply cord to
the range using the ground-link screw. The ground wire must
be attached first and must not contact any other terminal.
3. Use a ¼" nut driver to remove the hex washer head screws
from the terminal blocks.
4. Connect the neutral (center) wire to the center terminal
connector using one of the hex washer head screws.
Securely tighten screw for proper electrical connection.
D
C
B
A
A. Line 1
B. Green ground wire
C. Ground-link screw
D. Hex washer head screw
E. Silver-colored terminal
block screw
12
B
E
F
G
H
I
F. Ground link
G. Neutral (center) wire
H. Line 2
I. UL listed strain relief and
40- or 50-amp range
power supply cord
5. Connect the other 2 wires (lines 1 and 2) to the outer
aluminum terminal blocks.
6. Securely tighten screws for proper electrical connection.
7. Tighten strain relief screws.
8. Replace terminal block cover.
3-wire connection: Power supply cord
Use this method only if local codes permit connecting cabinet-
ground conductor to neutral wire of power supply cord.
1. Use a ¼" nut driver and remove the hex washer head screws
from the aluminum terminal blocks.
2. Connect the neutral (center) wire to the center terminal
connector using one of the hex washer head screws.
Securely tighten screw for proper electrical connection.
C
B
A
A. Line 1
B. Ground link
C. Hex washer head screw
D. Silver-colored terminal
block screw
3. Connect the other 2 wires (lines 1 and 2) to the outer terminal
screws on the terminal block.
4. Tighten strain relief screws.
5. Replace terminal block cover.
D
E
F
G
E. Neutral (center) wire
F. Line 2
G. UL listed strain relief
and 40- or 50-amp range
power supply cord