SPECIFICATIONS

Series 700 and 800 Viewing Heads
MODELS S702, S702PF, S702HF, S702HFPF, S706,
S706PF, AND MODELS S802, S802HF, AND S806
Electrical
Input Power: 22VDC to 26VDC, 150 mA MAX from Model
700ACSP or 700DCSP Signal Processor
Environmental
Viewing Head Sealing: NEMA TYPE 4/4X rated when the
molded connector ring is tightened with pliers and a UV
protection is provided for the cable by installing in conduit.
Ambient Temperature: -40°F to 185°F (-40°C to 85°C)
IR Detector Spec
S702, S702PF, S702HF, S702HFPF, S802, S802HF:
Germanium photodiode with spectral response 950nm to
1710nm (1/2 intensity points) and peak spectral response
at 1400nm
High Pass Filter Pickup: 33 Hz standard, 155 Hz high
frequency option (-HF)
IR Optical
Angle of View: 1 degree (1.45" dia. at 6 ft. or 3.7cm dia. at
1.8m)
UV Detector Spec
S706 & S706PF, S806: UVtron with spectral response 185nm
to 260nm and a peak response at 210nm
UV Optical
Angle of View: 5 degrees (1 inch per foot)
Cable & Connector
Signal Proc. to V.H.:
(Standard) Honeywell C330, 4 Conductor, 18 ga., shielded,
90C, Sunlight Resistant, 15 ft. long, with ITC rating for US
and CIC rating for Canada. (This rating permits use in
hazardous locations without a conduit.)
With PF option Honeywell C330 cable or 4 conductor, 22
ga. or larger with overall braided shield, 95% coverage, or
with shield over the signal line may be used for extension
purposes. Tie shield to ground at viewhead end and signal
processor end of cable. (Cable must be protected by a
conduit in hazardous locations.)
Dimensions
Refer to Fig. 8 and Fig. 9.
Model 700ACSP & Model 700DCSP Signal
Processer
Electrical: Model 700ACSP
Primary Input Power: 85-265VAC, 50-60 HZ, 0.07A Max.
fused (with either V.H. connected)
Battery Backup Voltage: 22VDC to 26VDC, 0.2A DC Max.
fused (with either V.H. connected)
Electrical: Model 700DCSP
Primary Input Power: 22VDC to 26VDC, 250 mA Max. fused
(with either V.H. connected)
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Battery Backup Voltage: 22VDC to 26VDC, 0.5A DC Max.,
fused (with either V.H. connected)
Outputs
Flame Relay: 2 form C contacts
Self-Checking Relay: 1 form C contact
Relay Contact Ratings: 5A at 125 VAC, 277 VAC, & 30 VDC;
1/8 HP 125 & 250 VAC
Analog Flame Signal: Isolated 0 to 20 mA or 4 to 20 mA
output for remote meters or DCS, 360 ohms maximum
resistance
Environmental
Ambient Temperature: 32°F to 140°F (0°C to 60°C)
Dimensions
Refer to Fig. 10 and Fig. 11.

APPROVALS

S70X/S80X Viewing Heads (Connector series and Pipe fit
series [PF])
CSA for CLASS I, DIV 2, GROUPS A, B, C, D & T4A
FM 7610/NEMA 4X and CLASS 1, DIV 2, GROUPS A, B, C, D
& T4A*
SIL 3 "Fit for Use"
IECEx CSA 10.0003 Ex nA IIC T4 Gc
-40<Ta<85ºC, -40<TA<185ºF
*IP67/NEMA 4/4X rating applies when connector ring is
properly tightened and cable is UV shielded
700ACSP and 700DCSP Signal Processors
CSA (C, US)
FM

INSTALLATION

When Installing These Products...
1. Read these instructions carefully. Failure to follow them
could damage the products or cause a hazardous
condition.
2. Check the ratings given in the instructions and one the
products to make sure the products are suitable for your
application.
3. Installer must be a trained, experienced, flame
safeguard control technician.
4. After installation is complete, check out product
operation as provided in these instructions.

Signal Processor Mounting

The 700ACSP and 700DCSP signal processors mount on a
standard 35mm DIN rail. They snap into place and may be
released from the rail using a flat screwdriver.