All panels must be in place when rigging.
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets as shown in Detail A.
Lifting brackets shall be centered around the unit center of gravity. Use wood
top skid when rigging to prevent rigging straps from damaging unit. Remove
4 screws to slide wood support through rectangular hole in rail.
Fig. 7 — Area Not To Be Drilled
• A 90-degree elbow must be used in the return duct or a
straight return duct must terminate with a grille securely
attached, so that if tools are dropped when working on the
unit, they will not enter the occupied psace.
• Units with electric heat require a 1-in. clearance for the
first 24 in. of ductwork.
• Outlet grilles must not lie directly below unit discharge.
Failure to follow these instructions on clearances and
90-degree ductwork and the location of outlet grilles could
result in personal injury and property damage from fall-
ing objects.
Unit
50HS
024
030
036
048
060
Fig. 6 — Suggested Rigging
• Secure all ducts to building structure. Flash, weather-
proof, and vibration-isolate duct openings in wall or roof
according to good construction practices.
Figure 8 shows a typical duct system with 50HS installed.
Table 2A — Minimum Airflow for Uninterrupted
024
330
Table 2B — Minimum Airflow for Uninterrupted
024
700
8
CHART A — UNITS WITH BASE RAIL
Shipping
A
Weight
Kg
Lb
mm
134
295
413
16.26
139
307
415
16.34
148
327
418
16.46
180
398
428
16.85
187
412
429
16.89
Electric Heater Operation — SI
MINIMUM AIRFLOW (L/s)
Unit Size
030
036
413
567
Electric Heater Operation — English
MINIMUM AIRFLOW (Cfm)
Unit Size
030
036
875
1200
B
in.
mm
in.
715.0
28.15
715.0
28.15
816.6
32.15
969.0
38.15
969.0
38.15
048
060
661
826
048
060
1400
1750