7 Inspection and maintenance
4
5
6
7
Fig. 7.7 Refitting the compact thermal module
• Insert the compact thermo module (9) in the integral
condensation heat exchanger (10).
• Tighten the four nuts (4) on the left/right sides until
the burner door fits closely and uniformly to the stop
surfaces.
• Reconnect the HT lead (5) and earth lead (6) to the
spark electrode.
• Insert the cables (8) on the fan motor and the cable
(7) on the gas fitting.
3
Fig. 7.8 Connecting the gas supply
• Reconnect the gas supply (3) to the gas valve, ensur-
ing that a new sealing washer is used and correctly
located. Use the spanner flat at the flexible gas line to
hold the gas fittings.
• Turn on the gas supply and test for soundness.
• Refit the air inlet pipe, ensuring that the blue seal in
the air intake pipe is correctly located.
42
7.3

Cleaning the condensation water siphon

10
9
8
Fig. 7.9 Cleaning the condensation water siphon
Danger!
Note that if the boiler is run with an empty
condensate trap there is a danger that fumes
might escape into the room and cause poison-
ing. For this reason, it is important to ensure
that the trap is topped up each time the unit is
cleaned.
• Remove the lower part (1) of the condensate water
siphon by turning the bayonet catch in anticlockwise
direction.
• Clean the siphon part section by rinsing it out with
water.
• Fill the lower part with water until about 10 mm below
the upper edge.
• Fasten the lower part again on the condensate water
siphon.
Instructions for installation and servicing ecoTEC