Reference for air-discharge chamber (field supply)
Required space around outdoor unit
If an air discharge chamber is used, the space shown below must be secured around the outdoor unit.
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
(1) Single-unit installation
CAUTION
(2) Multiple-unit installation
●
Installation in lateral rows
More than 11-13/16
More than 7-7/8
CAUTION
●
Installation in front-rear rows
Installation with intakes facing
intakes or outlets facing outlets
More than 59-1/16
CAUTION
The top and both sides must remain open.
If there are obstacles to the front and rear of the outdoor unit,
the obstacle at either the front or rear must be no taller than the
height of the outdoor unit.
More than 11-13/16
The front and top must remain open.
The obstacles must be no taller than the height of the outdoor unit.
More than 15-3/4
The front and both sides must remain open.
17
Unit: in.
Unit: in.
Installation with intakes facing outlets
More than 78-3/4
Unit: in.