Technical Specifications
Power Required, Kva
Power Distribution Unit
(PDU) required for all
GS1280 Models 3X-H7606-
Ax
Power Distribution Unit
(PDU) required for GS 1280
Models 32 and 64, 3X-
H7606-Bx
Physical Characteristics
Dimensions (H x W x D)
Shipping Dimensions
Installed Weight, base system 870 lb (395 kg)
Heat dissipation
Max Heat Output, Base Model
only, watts
Max heat Output, Base Model
only, Btu/hr
Typical Heat Output, Base
Model only, watts
Typical Heat Output, Base
Model only, Btu/hr
Airflow, cfm, minimum full
rack, each CPU rack
Airflow, cfm, maximum full
rack, each CPU rack
Airflow, cfm, minimum full
rack, power rack for Model 32
and 64
Airflow, cfm, maximum full
rack, power rack for Model 32
and 64
GS1280 Model 8
GS1280 Model 16
1 I/O Drawer, 1 SW
1 I/O Drawer, 1 SW
Shelf
Shelf
3.5
5.7
1 required; 2 for dual
2 required; 4 for dual
AC
AC
Not applicable
Not applicable
79 x 24 x 47 in (200 x 60 120 cm) (one 41U Rack)
86 x 32 x 48 in (217 x 92.5 142 cm) (one 41U Rack)
GS1280 Model 8
GS1280 Model 16
1,272 lb (577 kg)
3,405
6,810
11,622
23,243
2,430
3,700
8,297
12,632
912
1,562
1,404
2,454
DA - 11921 Worldwide — Version 24 — July 23, 2007
HP AlphaServer GS1280 Systems
GS1280 Model 32
GS1280 Model 64
1 I/O Drawer, 1 SW
1 I/O Drawer, 1 SW
Shelf
Shelf
10.1
18.7
2 required, dual AC
2 required, dual AC
included
included
2 required, dual AC
4 required, dual AC
included
included
GS1280 Model 32
GS1280 Model 64
2,118 lbs (961 kg)
4,800 lbs (2,176 kg)
14,820
28,440
50,581
97,066
8,000
14,800
27,304
50,513
1,800
1,800 x 2 racks
3,400
3,400 x 2 racks
1,324
1,455
1,508
1,685