PROGRAMMING
7.2

Function List

No.
Function
Primary Motor Settings
1
Motor full load current
2
Current limit
3
Minimum current
4
Start ramp time
5
Stop ramp time
6
Motor trip class
7
Current imbalance sensitivity
8
Undercurrent protection
9
Stall protection
Start/Stop Formats
10
Soft stop mode
Starter Functionality
20
Local/Remote operation
21
Relay output A functionality
22
Relay output B functionality
23
Relay output C functionality
Protection Settings
30
Phase rotation
31
Restart delay
32
Current imbalance
Set Points
40
Low current alarm
41
High current alarm
42
Motor temperature alarm
43
Field calibration
Analogue Output (Motor Current - % FLC)
50
4-20mA output range - max
51
4-20mA output range - min
Serial Communications
60
RS485 timeout
61
RS485 baud rate
62
RS485 satellite address
Auto Reset
70
Auto-reset - configuration
71
Auto-reset - number of resets
72
Auto-reset - group A & B delay
73
Auto-reset - group C delay
Secondary Motor Settings
80
Motor full load current
81
Current limit
82
Minimum current
83
Start ramp time
84
Stop ramp time
85
Motor trip class
86
Current imbalance sensitivity
87
Undercurrent protection
88
Stall protection
Protection Delays
90
Current imbalance trip delay
Read Only Data
100 Model Number
101 Fault History
Restricted Functions
110 Access code
111 Update access code
112 Function lock
113 Restore function settings
18
7.3
Default
1.
Setting
Range: Model Dependant (Amps)
-
Default Setting: Model Dependant (Amps)
350
350
Description: Sets the TMS7 for the connected motor's full load
1
current.
0
Adjustment: Set to the Full Load Current (amps) rating shown
10
on the motor nameplate.
5
20
2.
400
Range: 100 – 550 % FLC
0
Default Setting: 350% FLC
0
Description: Sets the current limit for the Constant Current start
11
mode.
10
0
700%
0
15
0
500%
50
105
300%
80
100
100%
100
0
0
4
Adjustment: The required setting for the Current Limit function
20
is installation dependant and should be set such that:
The motor is supplied with sufficient start current to enable
0
it to produce torque adequate to easily accelerate the
1
connected load.
5
Desired starting performance is obtained.
5
TMS7 ratings are not exceeded.
-
3.
350
350
Range: 100 – 550 % FLC
1
Default Setting: 350% FLC
0
Description: Sets the minimum current level for the Ramp Start
10
mode.
5
20
400
700%
3
-
500%
-
0
300%
0
0
0
100%
ME00070B

Function Descriptions

Motor Full Load Current
Current Limit
eg. Function 2. Current Limit = 350% x FLC
50%
ROTOR SPEED
( % Full Speed)
Minimum Current
Function. 2 Current Limit = 350% x FLC
Function. 3 Minimum Current = 200% x FLC
Function. 4 Start Ramp Time = 10 secs
50%
ROTOR SPEED
(% Full Speed)
100%
100%
TMS7 SERIES