3.2. STW Control Word Data

PDP003Z supports only speed control mode.
Bit Value
1
0
0
1
1
0
1
2
0
1
3
0
1
4
0
1
5
0
1
6
0
1
7
0
1
8
0
1
9
0
1
10
0
11
---
1
12
0
1
13
0
14
---
15
---
* RFG: Ramp Function Generator
** Operation is enabled, drive is in standstill and STW1 bit 4, 5, 6 = 0.
Name
ON
OFF
No Coast Stop
Coast Stop (OFF 2)
No Quick Stop
Quick Stop (OFF 3)
Enable Operation
Disable Operation
Enable Ramp Generator
Reset Ramp Generator
Unfreeze Ramp Generator
Freeze Ramp Generator
Enable Setpoint
Disable Setpoint
Fault Acknowledge
No meaning
JOG 1 ON **
JOG 1 OFF
JOG 2 ON **
JOG 2 OFF
Control By PLC
No Control By PLC
Device-specification
Net Control
Local Control
Net Reference
Local Reference
Device-specification
Device-specification
- 10 -
"Switched on" condition
Normal stop.
All "Coast Stop (OFF2)" commands are withdrawn
Coast stop.
All "Quick Stop (OFF3)" commands are withdrawn.
Quick Stop
The drive then runs-up to the setpoint.
Normal stop.
Output of the RFG is set to 0.
Freeze the actual setpoint entered by the RFG *.
The value selected at the input of the RFG is switched-in.
The value selected at the input of the RFG is set to 0.
Fault reset (0 -> 1)
VF-MB1/S15 drives with JOG 1 speed 1 (
Jogging stop, if "JOG 1" was previously ON. Stop drive
according to VF-MB1/S15 setting parameter.
VF-MB1/S15 drives with JOG 2 speed 2 (
Jogging stop, if "JOG 2" was previously ON. Stop drive
according to VF-MB1/S15 setting parameter.
The control word and main setpoint are activated.
The control word and main setpoint are inactivated.
(Reserved.)
PDP003Z control is enabled.
PDP003Z control is disabled.
PDP003Z reference is enabled.
PDP003Z reference is disabled.
(Reserved.)
(Reserved.)