Table SP-5 – Model P Projection Unit Heater Steam Capacities
2 Lbs. Steam 60 F Entering Air Temperature
Motor
Motor
Size
HP
RPM
42-P
1/25
1550
1150
64-P
1/20
1550
1150
80-P
1/20
1550
1150
102-P
1/8
1070
850
122-P
1/6
1070
146-P
1/6
1070
166-P
1/6
1070
202-P
1/4
1070
252-P
1/4
1070
280-P
1/2
1070
336-P
3/4
1120
384-P
3/4
1120
500-P
1-1/2
1120
600-P
1-1/2
1120
720-P
3
1120
42-P-L
1/25
1150
1150
64-P-L
1/20
1550
1150
80-P-L
1/20
1550
1150
102-P-L
1/8
1070
850
122-P-L
1/6
1070
146-P-L
1/6
1070
166-P-L
1/6
1070
202-P-L
1/4
1070
252-P-L
1/4
1070
280-P-L
1/2
1070
336-P-L
3/4
1120
384-P-L
3/4
1120
500-P-L
1-1/2
1120
600-P-L
1-1/2
1120
720-P-L
3
1120
Notes:
Constant speed units are rated at capacities shown in regular type; capacities in italic faced type apply only to units with multi-speed motors.
To determine BTU per hour capacities at various steam pressures and entering air temperatures, use conversion factors from Table SP-7, page 18.
Final temperatures at new conditions can be calculated by applying basic formula.
Table SP-6 – Maximum Spread (Ft.)
Unit No.
42P
64P
80P
Spread (Ft.)
15
17
Note:
The "spread" is the diameter of the comfort zone at floor level, projected by the Model P unit without the louver cone diffuser, based on two pounds steam pressure and 60 F entering air.
UH-PRC001-EN
Selection
Procedure
BTU
Condensate
Per Hour
EDR
Lbs Per Hr
41,300
172
33,600
140
65,500
273
52,800
220
80,600
336
65,100
271
101,800
424
106
87 ,900
366
124,400
518
129
152,000
633
157
173,000
720
179
210,200
838
208
249,800
1040
260
283,800
1180
294
333,400
1390
345
386,000
1610
400
496,000
2070
514
585,000
2440
605
705,000
2940
729
Low Final Temperature Models - Standard Model P Units With All Air Ports Open