Table PD-40 — Air Temperature Rise Across Electric Heaters (Degree F)
KW
Stages
5.00
1
6.00
1
10.00
2
12.00
2
13.80
2
17.40
2
17.60
2
23.00
2
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
kWx3414
Temp. Rise across Elect. Htr =
1.08xCFM
Notes:
1. The minimum allowable airflow for a 3 ton with a 17.4 KW heater is 1020 CFM.
2. The minimum allowable airflow for a 4 ton with a 17.4 or 17.6 KW heater is 1440 CFM.
3. The minimum allowable airflow for a 5 ton with a 23.0 KW heater is 1900 CFM.
36
Performance
Data
3 Ton
1
1200 CFM
Single Phase
Three Phase
WSC036A11
WSC036A3,A4,AW
13.2
15.8
26.3
31.6
36.4
45.8
Table PD-41 — 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)
KW
Stages
9.00
1
18.00
1
27.00
2
36.00
2
54.00
2
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
Temp. Rise across Elect. Htr =
Note:
1. Minimum allowable aiflow for a 6 ton with a 36.0 KW heater is 2450 cfm.
Table PD-42 — Electric Heater Temperature Rise Correction Factors
% Variation From Nominal CFM
Temperature Rise Multiplier
4 Ton
2
1600 CFM
Single Phase
Three Phase
WSC048A1
WSC048A3,A4,AW
9.9
11.9
19.8
23.7
27.3
34.4
34.8
6 Ton
2000
WSC072A3, A4, AW
14.2
28.5
42.7
56.9
1
kWx3414
1.08xCFM
- 20
- 15
- 10
1.25
1.17
1.11
5 Ton
3
2000 CFM
Single Phase
Three Phase
WSC060A1
WSC060A3,A4,AW
7.9
9.5
15.8
19.0
21.8
27.5
27.8
36.4
7½ Ton
3000 CFM
4000 CFM
WSC090A3, A4, AW
WS120A3,A4,AW
9.5
19.0
14.2
28.5
21.3
37.9
28.5
42.7
- 5
0
+5
+10
1.05
1.00
0.95
0.91
0.87
PKGP-PRC003-EN
10 Ton
+15
+20
0.83