Pxdr10.Drain.kit.installation.instructions.(Optional.for.new.construction) - Friedrich 920-087-09 (12/10) Installation And Operation Manual

Packaged terminal air conditioners & heat pumps
Table of Contents

Advertisement

PXDR10 Drain Kit Installation
Instructions (optional for new
construction)
NOTE:.
Determine.whether.drain.will.be.located.within.the.wall,.on.the.
indoor.side,.or.will.drain.to.the.exterior.of.the.building...Follow.
appropriate.instructions.below.depending.on.your.particular.
type.of.installation.
Internal Drain
NOTE:.
If.installing.an.internal.drain,.you.MUST.install.a.drain.kit.on.
the.wall.sleeve.before.the.wall.sleeve.is.installed.
1. Refer. to. Figure. 11. and. locate. the. drain. within. the. "Preferred".
area.of.best.drainage...Maintain.at.least.a.½".clearance.from.the.
embossed.area.
2. Using.the.mounting.plate.with.the.½".hole.as.a.template,.mark.
and. drill. two,. 3/16". mounting. holes. and. a. ½". drain. hole. in. the.
sleeve.bottom.
Figure 11
Drain Kit Location and Installation
IF THE DRAIN MUST BE
LOCATED IN THE OPTIONAL
AREA, THE FOAM INSULATION
MUST BE CUT AWAY AND
REMOVED TO ALLOW ACCESS
TO THE DRAIN.
10
OPTIONAL AREA
PREFERRED AREA-
NO FOAM INSULATION
3"
3. Remove.the.backing.from.the.gasket.and.mount.it.on.the.flat.side.
of.the.mounting.plate...(See.Figure.12,.Page.11)...Insert.the.drain.
tube.through.the.hole.in.the.gasket.and.mounting.plate.so.the.tube.
flange.will.be.against.the.wall.sleeve.
4. Position.the.assembly.beneath.the.drilled.holes.and.secure.it.with.
#10-24.x.½".machine.screws.and.lock.nuts.provided...Seal.the.tops.
of.the.screws.with.silicone.caulking..
5. Use.½".I.D..copper.tube,.PVC.pipe,.or.vinyl.hose.(obtained.locally).
to.connect.the.internal.drain.tube.to.the.drain.system.in.the.building.
6. Referring.to.Figure.12,.Detail.A,.Page.11,.locate.and.assemble.the.
(2).two.cover.plates.and.gaskets.over.the.drain.holes.at.the.rear.
of.the.wall.sleeve...Attach.them.with.the.#10.sheet.metal.screws.
provided...Make.certain.that.the.four.overflow.slots.at.the.rear.of.
the.wall.sleeve.are.not.blocked.(See.drawing.of.the.back.of.the.
sleeve.Figure.12,.Page.11).
7. If.a.deep.wall.extension.(PDXWSEXT).is.used,.after.installing.the.
field.supplied.flashing,.caulk.as.required...Be.sure.to.caulk.around.
the.flashing.and.the.wall.sleeve.where.the.hole.was.drilled.for.the.
drain.tube..
WALL SLEEVE
MOUNTING
PLATE
DRAIN TUBE
SIDE VIEW
FRONT VIEW
PXDR10
QUANTITY
2
COVER PLATES
1
MOUNTING PLATE
1
DRAIN TUBE
3
MOUNTING PLATE GASKET
4
#10 X ½" SHEET METAL SCREWS
2
#10-24 X ½ " MACH. SCREWS
2
#10-24 X ½" LOCKNUTS
SCREW
GASKET
NUT
FRP011
DESCRIPTION

Advertisement

Table of Contents
loading

Table of Contents