Heat Pump Systems - Honeywell VisionPRO TH8000 Series Installation Manual

Visionpro th8000 series touch-screen programmable thermostat
Hide thumbs Also See for VisionPRO TH8000 Series:
Table of Contents

Advertisement

Wiring
Shaded areas below apply only to TH8320/TH8321.
1H/1C Heat Pump (no auxiliary heat)
Rc
Power
[1]
R
[R+Rc joined by jumper]
O/B
Changeover valve
Y
Compressor relay
G
Fan relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
2H/1C Heat Pump (with auxiliary heat)
L
Equipment monitor [6, 7]
Aux/E Auxiliary/Emergency heat relay (Heat 2)
Rc
Power
[1]
R
[R+Rc joined by jumper]
Changeover valve
O/B
Y
Compressor relay
G
Fan relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
See [notes] below
[1]
Power supply. Provide disconnect means and overload protection as required.
[3] Optional 24VAC common connection.
[5]
O/B set to control as either O or B in installer setup.
[6]
If L terminal is used, 24VAC common (terminal C) must be connected.
[7] Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor
when set to Heat, Cool, or Off).
Wiring guide—heat pump systems
[5]
[5]
VisionPRO
2H/2C Heat Pump (no auxiliary heat)
Y2
Compressor 2 relay
Rc
Power
[1]
R
[R+Rc joined by jumper]
O/B
Changeover valve
Y
Compressor 1 relay
G
Fan relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
3H/2C Heat Pump (with auxiliary heat)
Y2
Compressor 2 relay
L
Equipment monitor [6, 7]
Aux/E Auxiliary/Emergency heat relay (Heat 2)
Power
[1]
Rc
R
[R+Rc joined by jumper]
O/B
Changeover valve
Y
Compressor 1 relay
G
Fan relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
5
TH8000 Series
TM
[5]
[5]
69-2693—01