Trane R Series Installation Operation & Maintenance page 114

R series rotary liquid chillers water-cooled and condenserless
Table of Contents

Advertisement

114
Controls Interface
Current Overload Protection
The UCM continually monitors compressor current to provide unit protection
in the event of an overcurrent or locked rotor condition. Protection is based on
the phase with the highest current and, if limits are exceeded, the UCM will
shutdown the compressor and will display an MMR diagnostic.
Leaving Chilled Water Temperature Control
If the Auto key is pressed and a remote chilled water setpoint has been
communicated, the UCM will control to the Remote Chiller Water Setpoint.
Otherwise, it will control to the front panel setpoint. Control is accomplished
by both staging compressors and modulating the slide valves on each
compressor.
Upon start-up, if the leaving chilled water temperature is dropping 5 F per
minute or faster, the chiller will not load further.
Table 25
Compressor(s) Current Limit Setpoints
vs. Chiller Current Limit Setpoint (CLS)
Number of compressors
System
CLS
One
120%
120
100%
120
80%
120
60%
120
40%
80
Chilled Water Reset (CWR)
As an option, the UCM will reset the chilled water temperature setpoint,
based on either the return water temperature, zone air temperature, or
outdoor air temperature. The 1U2 Module is necessary to preform CWR.
The following are selectable:
1. One of four RESET TYPEs, from top to bottom in order of reset:
no CWR
RETURN WATER TEMPERATURE RESET
OUTDOOR AIR TEMPERATURE RESET
The Clear Language Display will not permit more than one type of reset to be
selected in the Operator Settings Menu.
2. RESET RATIO Setpoints. For OUTDOOR AIR TEMPERATURE RESET,
there are both positive and negative reset ratios.
3. START RESET Setpoints
4. MAXIMUM RESET Setpoints. The maximum resets are with respect to
the chilled water setpoint.
No matter which type of reset is selected all parameters are factory set to a
predetermined set of values. Field adjustment of 2, 3, or 4 above, is usually
not required.
(70 - 125)
in operation
Two
120
100
80
60
40
RLC-SVX07A-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents