Wired Zone Sensor Setup Using Tracer
Summit
If a wired sensor is also attached to the
UCM, the next step will be to make the
wired sensor a backup or an averaged
input. This can be done as follows:
1. From the Main Menu, select the Setup
Pull Down Menu
2.Highlight the Unit Controllers option
and select the VariTrane UCM II/III/IV...
Editor
3.Select the UCM to be modified and
press the "OK" button
4.In the UCM II/III/IV... Editor, open the
wireless folder
5.Change the Wireless Receiver Name
from Not Assigned to the correct name
of the receiver. Open the first available
1
"Edit Wired Zone Sensor"
1
6.Averaged
, Primary Backup
3
Secondary Backup
.
7 . Adjust the value desired in the "Set
Point Weight"
4
field.
8.Once complete, press the okay button
to return to the UCM editor.
9.Press the "Save" button to save the
changes to the UCM.
Notes:
1
The Averaging choice means the sensed
temperature will be averaged with the
wireless sensors and set point tempera-
ture will be averaged according to the
set point vote selected in option 20.
2
First backup means the UCM will look
for a wired sensor first if the wireless
sensor fails.
3
Second backup means the UCM will
look for a wireless backup sensor first if
the wireless sensor fails.
4
Wired Set Point Weight determines the
weighting of the set point vote. The
range is 0-9. The number chosen is the
number of votes the sensor gets in the
determination of the set point. If "0" is
selected the sensor gets no vote. This is
VAV-SVX01B-EN
Wireless VAV
Systems
used to disable the thumbwheel.
Wireless Zone Sensor Setup Using the
Setup Tool:
The setup tool has a Green LED to
indicate power and red LED to signal a
transmission.
1. The first step is to move DIP switch 8 on
the receiver to the setup mode.
2.To setup the sensor, remove the front
cover of the zone sensor, insert the plug
into the keyed socket at the bottom of
the circuit board.
The display reads:
Trane Setup Tool
Press Any Key
Pressing any key produces the
following display
UCM Address?
Add Average
menu.
To assign the sensor as an averaging
2
, or
sensor to a specific UCM enter the
UCM Address (1-63) and press send.
The receiver will beep 3 times to
indicate a successful assignment.
The setup tool provides additional
capabilities as well. The sensor can be
added as an averaging sensor or as a
backup to another Wireless sensor. A
maximum of four (4) averaging sensors
and one (1) backup may be assigned to
a UCM. The set point vote can be
changed from 0-9 by pressing the "Set
Point Vote" button. The sensor use is
toggled by pressing the "AVERAGE/
BACKUP" button on the setup tool. The
send button executes the command.
The receiver will beep 3 times to
indicate a successful assignment.
In addition to adding a sensor the setup
tool allows the user to delete an
assigned sensor or purge all sensors
assigned to a particular UCM. These
options are selected by pressing the
" ADD/DELETE/PURGE" button. The
send button executes the command.
The receiver will beep 3 times to
indicate a successful assignment.
The service tool can be used to check if
the receiver is receiving the RF
transmissions. While in the default
screen:
UCM Address?
Add Average
Press "Send. " The receiver will beep
twice to indicate it received the signal.
The "BATTERY/SERIAL#" on the setup
tool reads and displays the sensor's
serial number and battery level.
To return to the main screen at any time
press the "Clear Screen" button.
The setup tool has an energy saver
mode that initiates after approximately
1 minute of inactivity. Pressing any key
00
twice will wake up the setup tool. While
1
in the energy saver mode the LCD
blanks and the red and green LED's
flash.
00
1
37