The following table briefly describes the typical behavior of various UCM configurations during normal operating modes.
Unoccupied
Cooling
Single
Control to cooling
Duct
setpoint.
Reheat
All types of local
reheat available to
keep zone above
heating setpoint.
Fan
Fan runs until valve
Series
is fully closed AND
reheat is off.
Fan
Fan off unless local
Parallel
reheat is on.
(temp.)
Fan
Fan off unless local
Parallel
reheat is on.
(flow)
VAV-SVX01B-EN
UCM Programming
and Operation
Heating
Morning Warm Up
Control to heating
Tracer may place
setpoint.
UCM in max flow and
supplies hot air.
Control to heating
Electric reheat is
Electric reheat is
available if using auto
available if using auto
changeover and the
changeover and the
supply air temperature
supply air temperature
(or auxiliary temperature) (or auxiliary temperature)
is below 70
o
F . Local
is below 70
hot water reheat is
hot water reheat is
always available to
always available to
keep the zone above
keep the zone above
the heating setpoint.
the heating setpoint.
Fan runs until valve
is fully closed AND
reheat is off.
Fan off unless local
Fan off unless local
reheat is on.
reheat is on.
Fan off unless local
Fan off unless local
reheat is on.
reheat is on.
Transition to occupied
Morning Cool Down
Tracer may place
UCM in max flow
and supplies cold
air. Control to
setpoint.
cooling setpoint.
All types of local
reheat available to
keep zone above
heating setpoint.
o
F . Local
Fan on.
Fan on.
Fan off unless local
reheat is on.
Fan off unless local
reheat is on.
Occupied
Cooling
Heating
Control to cooling
Control to heating
setpoint.
setpoint.
All types of local
Electric reheat is
reheat available to
available if using auto
keep zone above
changeover and the
eating setpoint.
supply air temperature
(or auxiliary temperature)
is below 70
hot water reheat is
always available to
keep the zone above
the heating setpoint.
Fan on.
Fan on.
Fan on if needed
Fan on if needed
for heat.
for heat.
Fan on if needed
Fan off unless local
for ventilation or
reheat is on.
reheat is on.
o
F . Local
15