Discovery Mode - Honeywell W8635A Installation Instructions Manual

Equipment interface module
Hide thumbs Also See for W8635A:

Advertisement

C7089B
OUTDOOR
TEMPERATURE
SENSOR
W8635A
L1
(HOT)
L2
SYSTEM
TRANSFORMER
1
1
FACTORY INSTALLER JUMPERS.
WIRE NUT
Fig. 6. Using wire nut to pigtail a connection when
three or more wires are terminated at one terminal.

Discovery Mode

Discovery mode begins when the T8635L Thermostat
and W8635 EIM are first installed and power is
connected:
— The W8635 EIM transmits information to the T8635L
Thermostat that indicates the maximum number of
stages that are enabled and the type of EIM
connected.
— The thermostat receives information from the W8635
and then sets the cycle rates and equipment types
automatically.
Stage Configuration
The W8635A automatically configures the T8635L for
two stages of heat and two stages of cool. If using the
W8635A and the T8635L on a one heat/one cool
application, set Installer Setup No. 5 and 8 to 1 when
configuring the T8635L Communicating Thermostat.
For configuration combinations, see Table 3.
T8635L
2
OT
OT
1
3
1
2
3
G
C
W1
R
W2
Y1
R H
R C
Y2
Fig. 5. Three zone configuration.
T8635L
2
OT
OT
1
3
4
5
6
Z
FAN
1
2
3
X
RELAY
HEAT 1
RELAY
HEAT 2
4
5
6
Z
RELAY
1
2
3
X
COOL 1
RELAY
COOL 2
RELAY
4
5
6
Z
1
2
3
X
TROL-A-TEMP
MODEL AOBD
ZONE DAMPER
Heat Stages
M13378
Cycle Rate
The thermostat automatically sets the cycle rate based
on the information it received during Discovery Mode.
See Table 4.
To change the default cycle rate settings:
— enter T8635L Thermostat Installer Setup and select
the desired cycle rate settings for each stage. (All
stages can be set between 1 and 12 cph.)
Table 4. Default Cycle Rate Settings.
W8635A
Equipment
Interface
Module
Electric Heat Setting
When using the W8635A on an electric heat application,
set the T8635L Thermostat Installer Setup No. 4 to 1.
This instructs the W8635A EIM to energize the fan with
any call for heat.
3
W8635A EQUIPMENT INTERFACE MODULE
T8635L
2
OT
OT
1
3
W8703A
OPEN
CLOSE
1
2
OPEN
CLOSE
3
OPEN
TR1
CLOSE
TR2
COM
OPTIONAL
TROL-A-TEMP
MODEL ARD-PC
OR MODEL ZD
Table 3. Stage Combinations.
Cool Stages
1
2
0
0
1
2
st
nd
1
2
Stage
Stage
Heat
Heat
6 cph
6 cph
L1
(HOT)
L2
EXTERNAL
40 VA
TRANSFORMER
M13430A
0
0
1
2
1
2
st
nd
1
2
Stage
Stage
Cool
Cool
3 cph
3 cph
69-1339—2