Page 1
YTA Series User’s Temperature Transmitters Manual (Hardware) Manual Change No. 08-013 Please use the attached sheets for the pages listed below in the following manuals. IM 01C50B01-01E (12th) Page and Item Contents of Correction Page 2-6, 7-6 Change Marking Code for CENELEC ATEX Type of ATEX Documentation Protection “n”.
Page 2
Caution for CENELEC ATEX (KEMA) Intrinsically • All wiring shall comply with local installation safe type requirements. (Refer to the installation diagram) Note 1. Model YTA110/KU2, YTA310/KU2 and Note 4. Maintenance and Repair YTA320/KU2 temperature transmitters for • The instrument modification or parts replacement by...
Dust Ignition Proof Type Caution for CENELEC ATEX (KEMA) Flameproof Caution for CENELEC ATEX Type of Protection “n” Type and Dust Ignition Proof Type Note 1. Model YTA110/KU2, YTA310/KU2 and Note 1. Model YTA110/KU2, YTA310/KU2 and YTA320/KU2 temperature transmitters for YTA320/KU2 temperature transmitters...
7. GENERAL SPECIFICATIONS Factory setting ( ) Tag No. Left blank if not specified in order Input sensor type “Pt100, 3-wire” if not specified in order Lower bound of calibration range “0” if not specified in order Upper bound of calibration range “100”...
Page 5
7. GENERAL SPECIFICATIONS [For Explosion Protected Types] For FOUNDATION Fieldbus explosion protected type, see IM 01C50T02-01E. Descriptions Code Item CENELEC ATEX (KEMA) Intrinsically safe, Flameproof approval and Type n combination [Intrinsically safe approval] Applicable standard: EN 50014, EN 50020, EN 50284 Certificate: KEMA 02ATEX1026X II 1G EEx ia IIC T4,T5 Ambient Temerature: -40 to 70°C for T4, -40 to 50°C for T5 Supply/Output circuit: Ui=30V, Ii=165mA, Pi=900mW, Ci=20nF, Li=660 H...