Burst Mode; Multidrop Mode - YOKOGAWA Dpharp vigilantplant EJA Series User Manual

Eja series, hart protocol
Hide thumbs Also See for Dpharp vigilantplant EJA Series:
Table of Contents

Advertisement

(15) Burst Mode

The transmitter continuously sends the data stored in it
when the burst mode is set on. Either one of measured
pressure variable, % output value, or 4 to 20 mA
output value can be selected and sent. The data is sent
intermittently as a digital signal at 75 ms intervals
when the transmitter is set in the burst mode. There-
fore, communication by the HART simultaneous
communicator is also possible.
Setting of Burst Mode
1. Device setup
4. Detailed setup
3. Output condition
4. HART output
3. Burst mode, 4. Burst option
EJA:
Burst option
********
PV
(ENTER)
% range/current
Process vars/crnt
Call up the Burst option, and set
HELP
DEL
ESC
ENTER
the data to be sent.
• Pressure variable (PV)
• % output value (% range/current)
• 4 to 20 mA output value (Process
EJA:
Burst mode
Off
On
Off
HELP
DEL
DEL
ESC
ENTER
(ENTER)
(SEND)
Call up the Burst mode and set to
On.
Then, Press SEND (F2).
To Release from the Burst Mode:
Call up the Burst mode display, and set to OFF.
vars/crnt)
F0234.EPS
2. HART COMMUNICATOR OPERATION

(16) Multidrop Mode

"Multidropping" transmitters refers to the connection
of several transmitters to a single communications
transmission line. Up to 15 transmitters can be con-
nected when set in the multidrop mode. To activate
multidrop communication, the transmitter address must
be changed to a number from 1 to 15. This change
deactivates the 4 to 20 mA analog output, sending it to
4 mA. The alarm current also is disabled.
Setting of Multidrop Mode
1. Device setup
4. Detailed Setup
3. Output condition
4. HART Output
1. Poll addr
EJA:
Poll addr
O
0
HELP
DEL
ESC
ENTER
Online
Utility
Auto Poll
HART Communicator
Auto Poll
No
No
Yes
HELP
DEL
DEL
ESC
ENTER
NOTE
1. When the address is set and the multi-drop
mode is set to "No" at the same time, Online
menus cannot be called up and displayed. Be
sure to turn the multidrop mode to "Yes" after
setting the address with "Poll addr."
2. When the same polling address is set for two
or more transmitters in multidrop mode,
communication with these transmitters is
disabled.
2-16
Call up the Poll addr and set the
polling address. (a number from 1 to
15)
And press SEND (F2) to send the
data.
(ENTER)
Call up the Auto Poll and set to
Yes.
IM 01C22T01-01E
F0235.EPS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents