Shielding And Grounding The Connecting Cable For A Remote Connection - Siemens SIMATIC S7-400 Installation Manual

Automation system, hardware and installation
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Wiring the S7-400
Figure 4-8 shows the methods described here. If the permissible potential
difference between grounding points is exceeded, you must install an equipotential
bonding conductor (copper conductor with a cross-section of ≥ 16 mm
CR
Send IM
Figure 4-8

Shielding and Grounding the Connecting Cable for a Remote Connection

Special Cases
For remote connections, you must use precut/preassembled connecting cables of
fixed length. When the connecting cables are laid, therefore, there may be excess
lengths. These must be coiled with a bifilar winding and deposited.
4-16
Shield/
protective
ground bar
< 7 V
Automation System S7-400 Hardware and Installation
2
).
ER
Receive IM
A5E00850741-01