2-2. Outdoor Unit

AVOID:
G
heat sources, exhaust fans, etc. (Fig. 3)
G
damp, humid or uneven locations.
DO:
G
choose a place as cool as possible.
G
choose a place that is well ventilated.
G
install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or
exhaust port is not blocked, and so that sufficient
space is ensured for maintenance to be carried out
without trouble. In general the top also must be unob-
structed. (Figs. 4a and 4b)
G
provide a solid base (level concrete pad, concrete
block, 4" × 1'4" (10 × 40 cm) beams or equal), a mini-
mum of 4" (10 cm) above ground level to reduce
humidity and protect the unit against possible water
damage and decreased service life. (Figs. 5a and 5b)
A solid base must not cover
CAUTION
the hole of the bottom plate.
G
install cushion rubber under unit's feet to reduce vibra-
tion and noise. (Fig. 5c)
G
use lug bolts or equal to bolt down unit, reducing vibra-
tion and noise.
G
install in a location where no antenna of a television or
radio exists within 10' (3 m).
Drain holes
Fig. 5a
Air intake
Concrete
or equal
Fig. 5b
Air intake
Min.
2" (5 cm)
Air intake
Min.
2" (5 cm)
Anchor bolts
(4 pcs.)
Min. 4" (10 cm)
5
NO
Hot air
Outdoor unit
Fig. 3
(CH1271)
Min. 2" (5 cm)
Valve
side
Min. 10"
(25 cm)
Air discharge
Min.
8" (20 cm)
Fig. 4a
(CH1872)
Min. 4" (10 cm)
Valve
side
Min. 10"
(25 cm)
Air discharge
Min.
1'4" (40 cm)
Fig. 4b
Fig. 5c
Exhaust fan
Heat source
Obstacle above
Min.
Min.
7' (2 m)
7' (2 m)
Ground
Min. 2" (5 cm)
Air intake
Obstacle above
Min.
Min.
7' (2 m)
7' (2 m)
Ground
Min. 4" (10 cm)
Air intake
Cushion rubber