Section 3-3-1:
VENTINg LAYOUT: Wall mounted termination.
Selection of components and details of venting layout should
adhere to the following guidelines:
Vent terminations must not be recessed in walls or siding.
All through-the–wall terminations within 6' (total) of the fireplace
must have a Montigo Heat Shield (RHS101) installed. See
Section 3-3-3.
All through-the-wall terminations beyond 6' of the fireplace must
have a Montigo Heat Shield (RHS8) installed. See Section 3-3-3.
Once the proposed venting layout has been determined refer to
Figure 14 to ensure the layout is acceptable.
Notes Wall Mounted Terminations: Top Vent
All measurements for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 14.
Wall mounted Terminations
The following details are some possible configurations for Wall
mounted terminations. See below.
The Venting graph: L42DF-ST*
Measure the vertical height from the fireplace hearth to the centre of the
termination and the horizontal run from the fireplace flue collar to the wall
flange of the termination. Plot on the Venting Graph Figure 14 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Unacceptable Installation)
If the vertical dimension from the hearth is 108" and the horizontal
run to the wall flange of the vent termination is 180", this would
NOT be an acceptable installation
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 78" and the horizontal
run to the wall flange of the vent termination is 54", this would be
an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 90" and
the horizontal run to the wall flange of the vent termination is 108",
this would NOT be an acceptable installation.
WARNING:
An inspection of the explosion relief flappers and door
MUST be made prior to lighting the fireplace. A faulty seal
on the door gasket and/or explosion ports will result in
products of combustion leaking into the living space and
may result in carbon monoxide poisoning.
XG0182 -112811
Installation
Acceptable vent run
within non-shaded area.
Figure 14. L42DF-ST* Top Vent Venting Graph for wall mounted terminations.
Figure 16. Top Vented, wall mounted installation with1 elbow (1 one 90° bend).
The vent run must comply with Venting Graph for Top vent, wall mounted
terminations, Figure 14.
Figure 16a. Top Vented, wall mounted Multi-elbow installation. See Venting
Graph for Top vent, wall mounted terminations, Figure 14.
L42DF-ST* Indoor Gas Fireplace
C
B
Unacceptable vent run
54"
within shaded area.
If your installation does not fall
30"
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
30" max.
15'foot Max.
30"min
Solid Section
Flex Section
Hearth
A
RHS8
54"Min.
RHS8 Heat
Shield
Termination
8'foot
Max.
Exterior
Wall
Page 11