Low Battery Alarm; Temp Alarm - Humminbird 343c Operation Manual

300 series
Hide thumbs Also See for 343c:
Table of Contents

Advertisement

voltage is equal to or less than the menu setting. The battery alarm will only sound for
the battery that is connected to the 300 Series™ Fishing System. The Low Battery Alarm
should be set to warn you when the battery voltage drops below the safety margin that
you have determined. For instance, if you are running a trolling motor (battery
operated), you would want to set the Low Battery Alarm to sound before the battery
voltage drops too low for it to be used to start your main, gasoline-powered engine.
To change the Low Battery Alarm setting:
1. Highlight Low Battery Alarm on the Alarms main menu.
2. Use the LEFT or RIGHT 4-WAY Cursor Control keys to change the Low Battery
Alarm setting. (Off, 8.5V - 13.5V, Default = Off)
detected by the 300 series™ reaches the Temp Alarm setting, which is either set in
degrees Fahrenheit or Celsius [International Models only]. For example, if the Temp
Alarm is set to 58 degrees Fahrenheit, and the water temperature falls from 60
degrees to 58 degrees, the Temp Alarm will sound. Similarly, if the water temperature
rises from 56 degrees to 58 degrees, the Temp Alarm will also sound.
To change the Temp Alarm setting:
1. Highlight Temp Alarm on the Alarms main menu.
2. Use the LEFT or RIGHT 4-Way Cursor Control keys to change the Temp Alarm
setting. (Off, 33-120 [Fahrenheit], 0-50 [Celsius], Default = Off)

Low Battery Alarm

Low Battery Alarm sounds when the input battery

Temp Alarm

Temp Alarm sounds when the water temperature
42

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents