Honeywell Tradeline T7300F series 2000 Installation Instructions Manual page 9

Commercial microelectronic conventional or heat pump thermostat
Table of Contents

Advertisement

T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
5. Press the increase
EEPROM identification code. (Example: 314 =
EEPROM ID 314.
6. Press the increase
base identification code. (Example: HP = heat
pump subbase.)
7. Press Run Program to exit the system test mode.
The system test times out after four minutes with-
out any key presses.
key again to display the
M4933A
key again to display the sub-
M10290
Set Keypad Lockout Switch
The dip switch 1 on the back of the thermostat activates
the lockout features. The switch must be set to the ON
position (up) to activate the lockout feature. See Fig. 7.
The factory-setting is off (down). Remove the thermostat
from the subbase and set the switch to ON if keypad
lockout is desired. The level of lockout is determined by
the Installer Setup numbers 25 and 40.
BACK OF THERMOSTAT
Fig. 7. Set keypad lockout dip switch 1 on back of
NOTE: If changing Installer setup number 25 or 40, set
dip switch 1 to ON prior to entering Installer
setup.
9
ON
1
1
2
1
DIP 1 IS ON
2
thermostat.
2
DIP 2 IS NOT USED
M10235
62-0125—3

Advertisement

Table of Contents
loading

Table of Contents