ENERGY MANAGEMENT SOFTWARE

Microprocessor-based controllers can combine control and
energy management functions in the controller to allow sensor
and data file sharing and program coordination. Energy
management functions can be developed via the above DDC
operators, math functions, and time clock values, or they can
be separate program subroutines.
A summary of energy management programs possible for
integration into microprocessor-based controllers follows:

Optimum Start

Based on measurements of indoor and outdoor temperatures
and a historical multiplier adjusted by startup data from the
previous day, the optimum start program (Fig. 5) calculates a
lead time to turn on heating or cooling equipment at the
optimum time to bring temperatures to proper level at the time
of occupancy. To achieve these results the constant volume AHU
optimum start program delays AHU start as long as possible,
while the VAV optimum start program often runs the VAV AHU
at reduced capacity. Unless required by IAQ, outdoor air
dampers and ventilation fans should be inactive during
preoccupancy warmup periods. For weekend shutdown periods,
the program automatically adjusts to provide longer lead times.
This program adapts itself to seasonal and building changes.
AHU ON
AHU OFF
6:00 AM
8:00 AM
ADAPTIVELY
ADJUSTED
NORMAL
LEAD TIME
OCCUPANCY
27
24
21
18
6:00 AM
8:00 AM
Fig. 5. Optimum Start.
12:00 NOON
10:00 AM
COOLING
COMFORT
LEVEL
HEATING
10:00 AM
12:00 NOON
TIME
C4311

Optimum Stop

The optimum stop program (Fig. 6) uses stored energy to
handle the building load to the end of the occupancy period.
Based on the zone temperatures that have the greatest heating
and greatest cooling loads, and the measured heating and
cooling drift rates, the program adjusts equipment stop time to
allow stored energy to maintain the comfort level to the end
of the occupancy period. This program adapts itself to
changing conditions.
AHU ON
AHU OFF
4:00 PM
3:00 PM
24
SUMMER
23
WINTER
22
21
3:00 PM
4:00 PM
Fig. 6. Optimum Stop.

Night Cycle

The night cycle program (Fig. 7) maintains a low temperature
limit (heating season) or high temperature limit (cooling season)
during unoccupied periods by cycling the air handling unit while
the outdoor air damper is closed. Digital control systems often
reduce fan capacity of VAV AHU systems to accomplish this
and reduce energy usage.
AHU ON
OPTIMUM
STOP
PERIOD
AHU OFF
4:30 PM
5:00 PM
22
18
16
5:00 PM
Fig. 7. Night Cycle.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
138
LEAD TIME
OF SHUTDOWN
OPTIMUM STOP
PERIOD
6:00 PM
5:00 PM
END OF
OCCUPANCY
NORMAL
COMFORT
CONTROL
LIMITS
RANGE
5:00 PM
6:00 PM
TIME
OPTIMUM
8:00 AM
12:00 MIDNIGHT
UNOCCUPIED PERIOD
12:00 MIDNIGHT
8:00 AM
C4312
START
PERIOD
M15137

Advertisement

Table of Contents
loading

Table of Contents