Location Considerations; Alcove Or Closet Installation; Important To Installer - Samsung DV456EWHDSU/AA User Manual

Gas and electric dryer
Hide thumbs Also See for DV456EWHDSU/AA:
Table of Contents

Advertisement

Available languages

Available languages

If the new dryer is being installed into an existing exhaust system, you must
make sure:
The exhaust
system meets all local, state, and national codes.
That a flexible
plastic duct is not used.
To Inspect and clean all lint buildup from inside the existing duct.
The duct is not kinked or crushed.
The exhaust
hood damper opens and closes freely.
The static pressure
in any exhaust system must not exceed 0.83 inches of water column,
or be
less than 0.
This can be measured
with the dryer running with a manometer
at the point where the exhaust
duct connects
to the dryer. A no-heat
setting should
be used. The dryer tumbler
should
be
empty and the lint filter clean.
IM PORTANT TO INSTALLER
Please read the following
instructions
carefully
before installing the dryer. These instructions
should be kept
for future reference.
Z_
Remove the door from all discarded
appliances
to avoid the danger
of a child suffocating,
WARNINe
LOCATION
CONSIDERATIONS
Locate the dryer where there is enough space at the front for loading the dryer, and enough space behind
for the exhaust system.
This dryer is factory-ready
for rear exhaust.
To exhaust out the bottom
or the right
or the left (electric model only), use the accessory
exhaust kit (sold separately).
Instructions
are included
with the kit. It's important
to make sure the room has enough fresh air. The dryer must be located where
there is no air-flow obstruction.
On gas dryers, adequate
clearance
as noted on the data plate must be maintained
to ensure adequate
air
for combustion
and proper dryer operation.
Do not install or store the dryer in an area where
it will be exposed
to water and/or weather.
Keep the dryer
area clear of combustible
materials,
casoline,
and other flammable
vapors and liquids. A dryer produces
combustible
lint. The area around the dryer should
be kept Lint-Free.
ALCOVE
OR CLOSET
INSTALLATION
You must exhaust the dryer to the outside
to reduce the risk of fi re when installed in an alcove or
wA_.,._closet.
No other fuel-burning
appliance
should
be installed in the same closet as the dryer.
WARNING:
To reduce the risk of fi re, you must exhaust the dryer to the outdoors.
See Exhaust
information
section.
Minimum
clearances
between
the dryer and adjacent
walls or other surfaces
are:
2" in front,
17" on top, 1" on either side, and 5" in the back.
The closet front must have two unobstructed
air openings
for a combined
minimum
total area of 72 in2
with 3" minimum
clearance
on the top and bottom. A Iouvered door with equivalent
space clearance
is
acceptable.
installing
your dryer 11
DV400-03170A
EN HUDSON-PJT
vl.indd
Sec3:ll
2012-01-20
N 1:58:28