Power Supply Cord
Direct Wire
Fire Hazard
Use 10 gauge somidcopper wire.
Use a UL misted strain relief.
Disconnect
power before making emectricamconnections.
Connect neutram wire (white or center wire) to center
terminal
(silver).
Ground wire (green or bare wire) must be connected
to
green ground connector.
Connect remaining
2 suppmy wires to remaining
2 termina_s (gored).
SecureBy tighten
amlemectrical connections.
Failure to do so can resuJt in death, fire, or
electrical
shock.
3. Assemble a 3/,,,(1.9 cm) UL listed strain relief (UL marking on
strain relief) into the hole below the terminal block opening.
Tighten strain relief screws just enough to hold the two clamp
sections together. Put power supply cord through the strain
relief. The strain relief should have a tight fit with the dryer
cabinet and be in a horizontal position.
A. Terminal block cover
B. External ground conductor
screw
C. Center, silver-colored
terminal block screw
D. Hold-down
screw location
E. Neutral grounding
wire (green with yellow stripes)
4.
Now complete installation following instructions
for your type
of electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)