Removing And Replacing The Gas Control Valve/Thermostat; Housekeeping; Anode Rod Inspection - Kenmore POWER MISER 153.331280 Owner's Manual

Ultra low nox gas water heater 40 & 50 gallon
Table of Contents

Advertisement

Removing
and Replacing
the Gas Control
Valve/Thermostat
IMPORTANT: The gas control valve/thermostat
is a standard
valve with a right-hand thread thermocouple.
Use only factory
authorized replacement parts.
Removing the Gas Valve:
1.
Turn the gas control knob on the combination gas control
valve/thermostat clockwise to the "OFF" position. NOTE:
Depress the dial stop on Robertshaw valves before turning
the gas control knob. See Lighting Instructions on the water
heater.
2.
Turn off the gas at the manual shut-off valve on the gas
supply pipe (Figure 3).
3.
Drain the water heater. Refer to "Draining" section and
follow the procedure.
4.
Disconnect the igniter wire from the igniter. NOTE: First
remove the igniter from the bracket by depressing front and
rear holding tabs and lift. Next remove igniter bracket from
the gas valve. Disconnect the thermocouple (right-hand
threads), pilot tube, and manifold tube at the gas control
valve/thermostat (Figure 25).
5.
Refer to "Gas Piping" section and disconnect the ground
joint union in the gas piping. Disconnect the remaining
pipe from the gas control valve/thermostat.
6.
To remove the gas valve, thread a correctly sized pipe into
the inlet and use it to turn the gas valve (counterclockwise.)
Do not use pipe wrench or equivalent to grip body.
Damage may result, causing leaks. Do not insert any sharp
objects into the inlet or outlet connections. Damage to the
gas valve may result.
Replacing the Gas Valve:
To replace the gas control valve/thermostat,
reassemble
in reverse order. When replacing the gas valve, thread a
correctly sized pipe into the inlet and use it to turn the gas
valve (clockwise.) DO NOT OVER TIGHTEN, damage may
result.
Be sure to use approved Teflon ® tape or pipe joint
compound on the gas piping connections and fitting on
the back of the gas control valve that screws into tank.
Be sure to remove the pilot ferrule nut from the new gas
control valve/thermostat.
Turn the gas supply on and check for leaks. Test all
connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak. Correct
any leak found.
Be sure tank is completely filled with water before lighting
and activating the water heater. Follow the "Operating
Instructions"
If additional information is required, contact Sears Service
at: 1-800-4-MY-HOME ® (1-800-469-4663).
®
TEFLON
is a registered trademark of E.I. Du Pont De Nemours and Company.
Housekeeping
Vacuum around base of water heater for dust, dirt, and lint on
a regular basis.
Fire and Explosion Hazard
• DO not obstruct _mbustion
air
o_nings
at the bottom of the
water heater.
Do not use or store fl_ammable
vapor products such as gasoline,
solvents
or adhesives
in the
_me
room or area near water
heater or other appliance,
• Visibly inspect _ame arrestor at
least on_
every six months and
clean if accumu_a_d Hnto
• Can cause
serious
injury or
death,
AT LEAST
ONCE
EVERY
SiX
MONTHS
A VISUAL
INSPECTION
SHOULD
BE MADE
OF THE
FLAME
ARRESTOR.
CLEAN
IF LINT ACCUMULATIONS
ARE
NOTICED.
INSTALLED IN SUITABLE AREA: To insure sufficient ventilation
and combustion
air supply, proper clearances from the water
heater must be maintained.
See Facts to Consider About the
Location
section.
Combustible
materials
such as clothing,
cleaning materials, or flammable liquids, etc. must not be placed
against or adjacent to the water heater because they could
catch on fire.
Anode
Rod Inspection
Property
Damage
Hazard
- Avoid water heater damage.
• Inspection and replacement of anode rod required.
The anode rod is used to protect the tank from corrosion.
Most
hot water tanks are equipped with an anode rod. The submerged
rod deteriorates to protect the tank. Instead of corroding the tank,
water ions attack and eat away the anode rod. This does not
affect the water's taste or color. The rod must be maintained to
keep the tank in operating condition.
Anode
deterioration
depends
on water
conductivity,
not
necessarily
water condition. A corroded
or pitted anode rod
indicates high water conductivity and should be checked and/
or replaced more often than an anode rod that appears to be
intact. Replacement
of a depleted anode rod can extend the
life of your water heater. Inspection
should be conducted by
calling the Sears Service Center for an authorized contractor.
At a minimum, the anode(s) should be checked annually after
the warranty period.
24

Advertisement

Table of Contents
loading

Table of Contents