- 3 wire cord
3-wire receptacle
(NEMA type 10-30R)
ELECTRICAL SHOCK HAZARD
Failure to disconnect power source before servicing
€o e
per
njuryo reve e ..............................................................................................
1 Turn off power supply to outlet.
2
Remove the screw securing the terminal block
access cover in the lower corner on the back of the
dryer.
3
Install a UL-approved strain relief according to the
power cord/strain relief manufacturer's instructions
in the power cord entry hole below the access
panel. At this time, the strain relief should be
loosely in place.
4
Thread an UNPLUGGED, UL-approved, 30 amp.
power cord, NEMA 10-30 type SRDT, through the
strain relief.
5 Attach the power cord neutral (center wire)
conductor to the SILVER colored center terminal on
the terminal block. Tighten the screw securely.
6
Attach the remaining two power cord outer
conductors to the outer, BRASScolored terminals
on the terminal block. Tighten both screws
securely.
ELECTRICAL SHOCK HAZARD
Do not make a sharp bend or crimp wiring/conductor
at
_
_Access
cover
_-t-------_
screw
___STeb,
om'cn
k'
Line 2
__---_-
_
(BRASS terminal)
,eut a
Dne 1
.....
(BRASS terminal)
_
Internal ground
(GREEN screw)
Terminal
screw
recovery
slot
If a terminal screw falls during cord installation, it can
be retrieved in the terminal screw recovery slot below
the access panel.
7
Follow manufacturer's guidelines for firmly securing
the strain relief and power cord.
8
Reinstall the terminal block cover.
DO NOT remove
internal ground in
a 3-wire system!!
Neutral
terminal
If moving dryer from a 4-wire system and installing it
in a 3-wire system, move the internal ground from the
center terminal back to the GREEN screw next to the
terminal
block.