Recommended Roof Opening & Weights
Unit Size
A
ERVe-20
22
ERVe-35
25
ERVe-45
27
ERVe-55
27
All dimensions are in inches. These weights include sheet
metal weights added together with the largest motors,
blowers and accessories for the units.
Position the unit roof opening such that the supply
discharge and exhaust inlet of the unit will line up
with the corresponding ductwork. Be sure to allow
for the recommended service clearances when
positioning opening (see Service Clearances).
Do not face the outdoor air intake of the unit into
prevailing wind and keep the intake away from any
other exhaust fans. Likewise, position the exhaust
discharge opening away from outdoor air intakes of
any other equipment.
When cutting only duct openings, cut opening 1-inch
(25 mm) larger than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof is
constructed of combustible materials, area within the
roof curb must be ventilated, left open, or covered
with non-combustible material which has an "R"
value of at least 5. If area within curb is open, higher
radiated sound levels may result.
Where the supply or warm air duct passes thru a
combustible roof, a clearance of one inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A.
A
1.63
1.63
EXHAUST
INLET
B
SUPPLY
OUTLET
Approx.
B
Weight (lbs.)
37
825
44.5
1100
51.5
1275
60
1550

Service Clearances

ERVe units require minimum clearances to perform
routine maintenance, such as filter replacement,
energy wheel cassette inspection, and fan belt
adjustment. Blower and motor assemblies, energy
recovery wheel cassette and filter sections are always
provided with a service door
or panel for proper
component
access.
D
D
Recommended Service Clearances
Unit Size
A
ERVe-20
24
ERVe-35
32
ERVe-45
32
ERVe-55
32
All dimensions are in inches.
Access Panel Description and
Location
4
5
Outdoor air filters
Frost control
1
Outdoor air sensors
Preheater and controls
Outdoor air intake damper
2
Supply blower and motor
Electric control center
3
Main disconnect
Energy wheel cassette
4
Exhaust air filters
Exhaust air intake damper
Exhaust blower and motor
5
Outdoor air intake damper actuator
B
C
A
B
C
D
24
42
35
24
48
43
24
54
43
24
60
44
3
2
1
Energy Recovery Ventilator