Appendix A Blower Performance Tables; Direct Drive; Standard Down Shot And Horizontal (036) - Goodman CPC SERIES Installation Instructions Manual

Light commercial self-contained packaged heating & cooling unit 3 ton - 6 ton cpc/cph series
Table of Contents

Advertisement

APPENDIX A BLOWER PERFORMANCE TABLES

STANDARD DOWN SHOT AND HORIZONTAL
EXTERNAL STATIC
SPEED TAP
PRESSURE (ESP)
LOW
MED
HIGH
EXTERNAL STATIC
SPEED TAP
PRESSURE (ESP)
LOW
MED
HIGH
NOTES:
Tables represent dry coil without filter, to co mp ensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %.
3 Ton models are shipped from the facto ry with speed tap set on LOW.

DIRECT DRIVE

CPC/H036 DIRECT DRIVE DOWN SHOT
STAN DARD
CFM
in w.c.
0.10
1287
0.20
1233
0.30
1176
0.40
1107
0.50
1044
0.60
965
0.10
1476
0.20
1421
0.30
1334
0.40
1255
0.50
1180
0.60
1085
0.70
964
0.30
1455
0.40
1367
0.50
1277
0.60
1180
0.70
1080
0.80
922
CPC/H036 DIRECT DRIVE HORIZONTAL
STAN DARD
CFM
in w.c.
0.10
1296
0.20
1245
0.30
1174
0.40
1103
0.50
1013
0.10
1502
0.20
1449
0.30
1396
0.40
1335
0.50
1273
0.60
1153
0.70
996
0.20
1516
0.30
1454
0.40
1392
0.50
1273
0.60
1183
0.70
1092
0.80
920
17
AMPS
WATTS
1.66
350
1.63
342
1.59
332
1.55
320
1.51
312
1.45
296
2.08
446
2.03
432
1.96
414
1.90
396
1.84
386
1.78
368
1.70
344
2.31
490
2.25
476
2.16
454
2.09
438
2.02
418
1.90
386
AMPS
WATTS
1.67
356
1.60
334
1.56
325
1.52
316
1.46
300
2.10
456
2.06
444
2.02
432
1.97
418
1.91
404
1.83
380
1.71
346
2.36
506
2.31
496
2.26
486
2.17
458
2.09
441
2.02
424
1.90
390
RPM
770
815
858
891
924
957
866
885
918
945
971
990
1023
962
984
1006
1025
1039
1067
RPM
764
830
861
891
935
836
864
891
916
940
973
1017
940
960
979
1006
1023
1039
1067

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents