Checkmg Functional Members; Ac Receptacles; No-Fuse Breaker - Robin America RGV7500 Service Manual

Table of Contents

Advertisement

'
...^
.
:.
.
9. CHECKING FUNCTIONAL MEMBERS
9-1 VOLTMETER
Check the voltmeter if it is turned on by applying
specific voltage. Voltmeter cannot be checked with
circuit tester because its resistance is too large.
0
Check that no disconnection nor short-circuit
occurs with a tester, and the internal resistance
is around O O k ohms normally.
@
Turn on the commercial power supply input
and check the indication.
9-2 AC RECEPTACLES
Using a "Dr. Robin" or a circuit tester, check con-
tinuity between the two terminals at the rear of
the AC receptacles while the receptacle is
mounted on the control panel. When continuity is
found between the
output
terminals of the recep-
tacle with a wire connected across these termi-
nals, the AC receptacle is normal. When the wire
is removed and no continuity is found between
these terminals, the receptacles are also normal.
9-3 NO-FUSE BREAKER
Check continuity between each of two terminals
at the rear of the no-fuse breaker while it is
mounted on the control panel. Normally, there is
continuity between each of the
two
when the no-
fuse breaker is on while there is no continuity when
the no-fuse breaker is
off.
VOLTMETER
Fig. 9-7
Fig. 9-2
I
Fig.
9-3
-
29-