WARNING! REMOVAL OF THE SMOKE ALARM BATTERY AND DISCONNECT-
ING or LOSS OF A.C. POWER WILL RENDER THE SMOKE ALARM INOPERATIVE.
ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm (maximum
80mA for originating unit with 24 devices interconnected).

1. RECOMMENDED LOCATIONS FOR ALARMS

• Locate the first alarm in the immediate area of the bedrooms. Try to monitor
the exit path as the bedrooms are usually farthest from the exit. If more than
one sleeping area exists, locate additional alarms in each sleeping area.
• Locate additional alarms to monitor any stairway as stairways act like chim-
neys for smoke and heat.
• Locate at least one alarm on every floor level.
• Locate an alarm in every sleeping room.
• Locate an alarm in every room where electrical appliances are operated (i.e.
portable heaters or humidifiers).
• Locate an alarm in every room where someone sleeps with the door closed.
The closed door may prevent an alarm not located in that room from waking
the sleeper.
• Smoke, heat, and combustion products rise to the ceiling and spread horizon-
tally. Mounting the smoke alarm on the ceiling in the center of the room
places it closest to all points in the room. Ceiling mounting is preferred in
ordinary residential construction.
• For mobile home installation, select locations carefully to avoid thermal
barriers that may form at the ceiling. For more details, see MOBILE HOME
INSTALLATION.
• When mounting an alarm on the ceiling, locate it at a minimum of 4" (10 cm)
from the side wall (see FIGURE 1).
• When mounting the alarm on the wall, use an inside wall with the top edge
of the alarm at a minimum of 4" (10 cm) and a maximum of 12" (30.5 cm)
below the ceiling (see FIGURE 1).
• Put smoke alarms at both ends of a bedroom hallway or large room if the
hallway or room is more than 30 feet (9.1 m) long.
• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft
(0.9m) of the highest point (measured horizontally). NFPA 72 states: "Smoke
alarms in rooms with ceiling slopes greater than 1 foot in 8 feet (.3m in 2.4
m) horizontally shall be located on the high side of the room." NFPA 72
states: "A row of detectors shall be spaced and located within 3 ft (0.9m) of
the peak of the ceiling measured horizontally" (see FIGURE 3).