White Mountain Hearth DVP42FP Installation Instructions And Owner's Manual

White Mountain Hearth DVP42FP Installation Instructions And Owner's Manual

The tahoe direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

The Tahoe Direct Vent Zero Clearance
Gas Fireplace Heater
Installer: Leave this manual with the appli-
ance.
Consumer: Retain this manual for future refer-
ence.
WARNING: If the information in these instruc-
tions are not followed exactly, a fire or explosion
may result causing property damage, personal
injury or loss of life.
— Do not store or use gasoline or other flamma-
ble vapors and liquids in the vicinity of this or
any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas suppli-
er's instructions.
If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.

INSTALLATION INSTRUCTIONS

OWNER'S MANUAL
UL FILE NO. MH30033
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA only)
or mobile home, where not prohibited by state or local
codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified
kit is used.
WARNING: If not installed, operated and maintained
in accordance with the manufacturer's instructions,
this product could expose you to substances in fuel or
from fuel combustion which can cause death or seri-
ous illness.
AND
DIRECT VENT
GAS FIREPLACE HEATER
MODEL SERIES
MILLIVOLT STANDING PILOT
DVP42FP3(0,1,2,3)(N,P)-2
DVP48FP3(0,1,2,3)(N,P)-2
INTERMITTENT PILOT
DVP42FP7(0,1,2,3)(N,P)-2
DVP48FP7(0,1,2,3)(N,P)-2
REMOTE RF MODELS
DVP42FP9(1,3)(N,P)-2
DVP48FP9(1,3)(N,P)-2
GAS-FIRED
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for White Mountain Hearth DVP42FP

  • Page 1: Installation Instructions

    The Tahoe Direct Vent Zero Clearance Gas Fireplace Heater Installer: Leave this manual with the appli- ance. Consumer: Retain this manual for future refer- ence. WARNING: If the information in these instruc- tions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Section Page Important Safety Information ... 3 Safety Information for Users of LP Gas ... 4 Requirements for Massachusetts ... 5 Introduction ... 6 Specification ... 7 Fireplace Dimensions ... 7 Clearances ... 8 Locating Fireplace ... 8 Gas Supply ...
  • Page 3: Important Safety Information

    IMPORTANT SAFETY INFORMATION Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly. DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED • If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
  • Page 4: Safety Information For Users Of Lp Gas

    SAFETY INFORMATION FOR USERS OF LP GAS Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precau- tions which can protect both you and your family from an accident.
  • Page 5: Requirements For Massachusetts

    REQUIREMENTS FOR MASSACHUSETTS For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:...
  • Page 6: Introduction

    • Installation of any damaged fireplace or vent system component. • Modification of the fireplace or direct vent system. • Installation other than as instructed by Empire Comfort Systems, Inc. • Improper positioning of the logs, glass door or decorative rock.
  • Page 7: Specification

    Input Btu/hr Maximum Btu/hr Minimum (millivolt only) KWH (Maximum) (Minimum) NAT. Orifice Air Shutter Opening Orifice Air Shutter Opening Height without standoff Width Depth Gas Inlet Shutoff Valve (Pipe) Remote Control Options & Accessories 21759-6-0608 SPECIFICATIONS DVP42 28,000 19,000 #38 (.1015) P-203 1/8"(3.2mm) #52 (.0635")
  • Page 8: Clearances

    Clearance to Combustibles Back 0" (0 mm) Side 0" (0 mm) Floor 0" (0 mm) Top Stand-off 0" (0 mm) Top Framing Edge 3" (76 mm) Figure 2 Combustible Material No greeting cards, stockings or ornamentation of any type should be placed on or attached to the fireplace.
  • Page 9: Gas Supply

    The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code. Recommended Gas Pipe Diameter Pipe Length Schedule 40 Pipe Inside Diameter Nat.
  • Page 10: Rear Vent Conversion

    REAR VENT CONVERSION VERTICAL VENTING Note : It is recommended that the flue cover plate tab be pulled outward prior to removal. This will ensure that the plate is not accidentally dropped inside the rear air chamber. FLUE COVER PLATE (See note above) INLET VENT COVER PLATE...
  • Page 11: Installation

    Framing and Finishing 1. Choose unit location. 2. Frame in fireplace with a header across the top. It is important to allow for finished face when setting the depth of the frame. 3. Attach fireplace to frame using adjustable frame. Preset depth to suit facing material (adjustable to 1/2", 5/8"...
  • Page 12 Flush Mount Mantel Installation (Figure 10) The fireplace must extend 3/4" beyond finished wall surface when using a flush mount mantel. Refer to Figure 10 to locate nailing flanges on fireplace sides. Mark and drill two (2) 1/8" holes into fireplace side to mount each nailing flange.
  • Page 13 Flush Wall Installation FINISHED WALL 3! OF NON-COMBUSTIBLE MATERIAL FRONT TRIM OR NON- COMBUSTIBLE MA TERIAL (INSTALLA TION IS OPTIONAL) JOINT BETWEEN FINISHED WALL AND UNIT SEALED WITH 300° F, 149° C SEALANT MATERIAL (SEALANT IS OPTIONAL) Figure 12 Combustible Surround Installation COMBUSTIBLE SURROUND FINISHED WALL 2 X 4...
  • Page 14: Installation

    HORIZONTAL ONLY, STRAIGHT OUT THE BACK " A" PIPE LENGTH "A" "B" 6"(152mm) 5 1/8"(130mm) to 6 /2"(165mm) 9"(229mm) 8 1/8"(206mm) to 91/2"(241mm) 12"(305mm) 11 1/8"(283mm) to 12 1/2"(317mm) Figure 15 VERTICAL, 90° ELBOW TO HORIZONTAL OUT THE WALL "A" "B"...
  • Page 15: Venting Fireplace - Top

    VENTING FIREPLACE - TOP To Use the Vent Graph (Figure 19) 1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line.
  • Page 16 VENTING FIREPLACE - TOP (continued) Below Grade Installation When it is not possible to meet the required vent terminal clearances of 12" (305mm) above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178mm) below grade level. The 7"...
  • Page 17 Figure 23 MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW OFF TOP OF FIREPLACE FIREPLACE HARD ELBOW DIMENSIONS SERIES "A" "B" DVP42FP 43-1/2" 5" (1105mm) (127mm) DVP48FP 43-1/2" 5" (1105mm) (127mm) FIREPLACE FLEX PIPE 90 DEGREE BEND SERIES "A"...
  • Page 18: Examples - Top Vent Run

    EXAMPLES - TOP VENT RUN 24” 24” MINIMUM CLEARANCE TO COMBUSTIBLES Figure 27 Figure 26 Figure 28 Page 18 21759-6-0608...
  • Page 19: Venting Examples When Using A Dva47 Adaptor

    VENTING EXAMPLES WHEN USING DVA47 ADAPTOR Vertically Off Top of Fireplace Only Figure 30 Figure 29 Figure 31 21759-6-0608 Page 19...
  • Page 20: Dvvk-4Fv Direct Vent Termination Kit

    DVVK-4FV DIRECT VENT TERMINATION KIT This termination kit can only be used with Empire Comfort Systems direct vent fireplaces listed for use with DVVK-4FV Vertical Flex Vent Kit. Please review the instructions packaged with your fireplace and verify the fireplace model number. Check that this flex vent system is listed for use with your fireplace model prior to starting the installation.
  • Page 21 DVVK-4FV DIRECT VENT TERMINATION KIT (cont.) PRE-INSTALLATION INFORMATION: Items Required For Installation: Tools Phillips Screwdriver Hammer Saw and/or saber saw Level Measuring Tape Electric Drill and Bits Pliers Square Tin Snips Before You Start: Plan your installation. Read these instructions and the fireplace installation manual before installing unit and vent system. Set unit in place and survey how best to vent the unit.
  • Page 22 DVVK-4FV DIRECT VENT TERMINATION KIT (cont.) Step-By-Step Installation For Flex DV Kit Unpack vent components and check all items for shipping damage. For this venting system to operate as designed it is depen- dent on the use of all parts and procedures detailed in these instructions.
  • Page 23 DVVK-4FV DIRECT VENT TERMINATION KIT (cont.) 10. With the flex vent assembly and the 48” long hard pipe components laid out on the floor, begin securing these parts together. First, apply a generous bead of silicone sealant to the inside of the 4” diameter flex flue (not the end with the pre-installaed connector), then slide the flex flue over the 4”...
  • Page 24 DVVK-4FV DIRECT VENT TERMINATION KIT (cont.) 17. To attach the vent connections at the fireplace, be sure the 7” diameter adapter collar has been installed per step 3. Apply a bead of silicone sealant to the 4” diameter flex connector, then slide the flex pipe adapter collar into the fireplace flue collar and secure by installing a minimum of two (2) screws through the flue collar and into the adapter.
  • Page 25 DVVK-4FV DIRECT VENT TERMINATION KIT (cont.) Venting Support Straps (As Req'd.) 35 ft. Max Note: DVVK-4VF Kit Maximum Height (including fireplace) Is 13’. To Extend Vent Run, an Additional Vent Extension Kit Is Necessary 21759-6-0608 Vertical Termination Storm 4' Long Rigid Pipe Collar Roof Flashing...
  • Page 26: Dvvk-4Fv Direct Vent Termination Kit

    DVVK-4FV DIRECT VENT TERMINATION KIT (cont.) Item Number 4”/7” Vertical Termination Cap Roof Support Kit 2 Ply Alum Flex 4” Diameter by 6 ft. 2 Ply Alum Flex 7” Diameter by 6 ft. 4”/7” x 48” Rigid Pipe Assembly Firestop Thimble Assembly Roof Flashing (0/12 to 6/12) 7”...
  • Page 27: Venting Fireplace - Rear

    To Use the Vent Graph (Figure 39) 1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line. 2. From the point of this intersection, draw a vertical line to the bottom of the graph.
  • Page 28: Examples - Rear Vent Run

    Figure 40 Model DVP42 DVP48 Figure 41 Page 28 EXAMPLES - REAR VENT RUN Maximum Pipe Length H1 24" 18" Model Maximum Pipe Length H1 DVP42 24" DVP48 6" Figure 42 Figure 43 21759-6-0608...
  • Page 29: Dvvk-4Re Vent Kit Installation Instructions

    DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS CAUTION: Sharp edges, use protective gloves when installing. Tools Needed for Installation: Sheet metal snips 5/16” nut driver Phillips head screwdriver - #2 High temperature sealant or furnace cement rated for continuous use at 1,000 F minimum Measuring tape Parts Verification...
  • Page 30 DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS (cont.) VINYL SIDING KIT DV822 OUTSIDE MOUNTING PLATE MEASURE OUTSIDE WALL Figure 46 EXT. WALL SURFACE OR VINYL SIDING KIT FLUE PIPE CUT 2 ½” BEYOND EXTERNAL WALL SURFACE OR VINYL SIDING KIT. Figure 47 Page 30 7.
  • Page 31: Dvvk-4Re Vent Kit Installation Instructions

    DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS (cont.) Follow correct option according to venting method. Connecting Directly to Fireplace If the air inlet and flue outlet tubes are to be connected directly to the unit (no rigid venting system is being used), then the gasket provided must be used to seal the 4”...
  • Page 32: Dvvk-4F Flex Vent Instructions - Top Vent Only

    DVVK-4F FLEX VENT INSTRUCTIONS - TOP VENT ONLY The DVVK-4F FLEX VENT KIT includes the following components: • (1) Horizontal Termination Cap • (1) 4-foot section of Flex vent with spacers (4" flue/7" outer pipe) • (1) 4" dia. Flue adapter collar Flex venting can be installed either vertically or horizontally off of the DVP36 Series fireplaces.
  • Page 33: Termination Clearances

    TERMINATION CLEARANCES Termination clearance for buildings with combustible and noncombustible exteriors. Figure 54 Vertical Sidewall Installations Important! Minimum clearance between vent pipes and combustible materials is three (3") (76mm) on top, and (1") (25mm) on bottom and sides. Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the siding.
  • Page 34: Vent Clearances

    *Clearance above grade, veranda, porch, deck or balcony [*12 inches (30cm) minimum] clearance to window or door that may be opened [*12 inches (30cm) minimum for appliances < 100,000 Btuh (30kW) clearance to permanently closed window [minimum 12 inches (30cm) recommended to prevent condensation on window] vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (60 cm) from...
  • Page 35: Vent System Identification

    WALL THIMBLE (MAXIMUM OF TWO 90 ELBOWS) Special Venting Components (Simpson Duravent) See Empire Comfort Systems Retail Price List for Simpson Duravent part numbers and pricing. Special DV Vent Kits Available from Empire Comfort Systems, Inc. dealers. DVVK-4VP...
  • Page 36 WALL THIMBLE (MAXIMUM OF TWO 90 ELBOWS) Special Venting Components (Simpson Duravent) See Empire Comfort Systems Retail Price List for Simpson Duravent part numbers and pricing. Special DV Vent Kits Available from Empire Comfort Systems, Inc. dealers. DVVK-5RP...
  • Page 37: 5" X 8" Venting Framing And Finishing

    8" VENTING FRAMING AND FINISHING Installing Support Brackets (Figure 58) A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around the pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 8 inch diameter pipe and elbows and 1 inch clearance on both sides and bottom of the 8 inch dia.
  • Page 38 8" VENTING FRAMING AND FINISHING (continued) Figure 60 Figure 62 See Horizontal Termination Page 41 and Vertical Termination Pages 43 and 44. Figure 61 Page 38 21759-6-0608...
  • Page 39: 4" X 6⅝" Venting Framing And Finishing

    6 ⅝" VENTING FRAMING AND FINISHING Installing Support Brackets (Figure 63) A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around the pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 6 ⅝...
  • Page 40 6 ⅝" VENTING FRAMING AND FINISHING (continued) Figure 65 Figure 66 Page 40 Figure 67 See Horizontal Termination Page 41 and Vertical Termination on Pages 43 and 44. 21759-6-0608...
  • Page 41: Horizontal Termination

    HORIZONTAL TERMINATION NOTE: Termination cap should pass through the wall firestop from the exterior of the building. Adjust the termination cap to its final exterior position on the building. Warning: Termination cap must be positioned so that arrow is pointing up. Attach the termination cap with the four wood screws provided.
  • Page 42: Dvvk-5F Flex Vent Instructions

    DVVK-5F FLEX VENT INSTRUCTIONS The DVVK-5F FLEX VENT KIT includes the following components: • (1) Horizontal Termination Cap • (1) 4-foot section of Flex vent with spacers (5" flue/8" outer pipe) Flex venting can be installed either vertically or horizontally off of the DVP Series fireplaces. When installing a horizontal vent run from top connections, maintain at least ½"...
  • Page 43: Vertical Termination

    Locate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this nail through this center point. Make the outline of the roof hole around this center point. NOTE: Size of the roof hole dimensions depend on the pitch of the roof.
  • Page 44 If damage occurs to the combustion chamber, it must be replaced by a qualified service person. Contact Empire Comfort Systems, Inc. for replacement parts. Vertical Through the Roof Applications (Figure 76) Your Gas Fireplace has been approved for: a) Vertical installations up to 40 feet in height.
  • Page 45: Log Placement (4 Log Set)

    LOG PLACEMENT (4 LOG SET) Before you begin: If you are installing logs into the DVP42 or DVP48 model then this fireplace is supplied with a set of three ceramic fiber logs. Do not handle these logs with your bare hands. Always wear gloves to prevent skin irritation from ceramic fibers.
  • Page 46: Operating Instructions

    OPERATING INSTRUCTIONS 750 Millivolt System The standing pilot (750 millivolt system) is a continuous burning pilot. The pilot remains ON even when the main burner is OFF. When you ignite the pilot, the thermopile produces millivolts (electrical current) which energizes the magnet in the gas valve. After 30 seconds to 1 minute time period you can release the gas control knob and the pilot will stay ON.
  • Page 47: Operating Instructions

    OPERATING INSTRUCTIONS (continued) STANDING PILOT OPERATING INSTRUCTIONS Remote/Off/On Switch The fireplace is equipped with a Remote/OFF/ON switch. A wire harness is attached to the Remote/OFF/ON switch. The red, black and green (wires) female push-ons attach to the Remote/OFF/ON switch. At the opposite end of the wire harness, the black and green (wires) female push-ons attach to the gas valve.
  • Page 48: Standing Pilot Wiring Diagram

    STANDING PILOT WIRING DIAGRAM (OPTIONAL) THERMOSTAT (OPTIONAL) WALL SWITCH Figure 82 Page 48 21759-6-0608...
  • Page 49: Standing Pilot Lighting Instructions

    STANDING PILOT LIGHTING INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.
  • Page 50: Standing Pilot Troubleshooting

    STANDING PILOT TROUBLESHOOTING With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.
  • Page 51: Intermittent Pilot Operating Instructions

    INTERMITTENT PILOT OPERATING INSTRUCTIONS The intermittent pilot (120/24 volt system) is ON when the main burner is ON. When the main burner is OFF the intermittent pilot is OFF. The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip of the flame rod.
  • Page 52: Intermittent Pilot Lighting Instructions

    INTERMITTENT PILOT LIGHTING INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property A. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
  • Page 53: Intermittent Pilot Troubleshooting

    The 24 volt system. Type of gas being used and that shown on the rating label. The Service Department at Empire Comfort Systems, Inc. may be contacted to assist in servicing furnace. Servicing the Pilot and Main Burners, Pilot Orifice, and Main Burner Orifices: Disconnect the gas supply at the inlet to the...
  • Page 54 INTERMITTENT PILOT TROUBLESHOOTING Safety Lockout S8600H provides 100 percent shutoff, or safety lockout. A timer starts timing the moment the trial for ignition starts. Ignition spark continues only until the timed trial for ignition period ends. Then the module goes into safety lockout. Lockout de-energizes the first main valve operator and closes the first main valve in the gas control, stopping pilot gas flow.
  • Page 55 Important 1. The following service procedures are provided as a general guide. 2. Meter readings between gas control and ignition module must be taken within the trial for ignition period. Once the igni- tion module locks out, the system must be reset by setting the thermostat down for at least one minute before continuing.
  • Page 56 INTERMITTENT PILOT TROUBLESHOOTING (continued) Page 56 21759-6-0608...
  • Page 57: Intermittent Pilot Troubleshooting

    INTERMITTENT PILOT TROUBLESHOOTING (continued) Green LED Flash Code (X + Y) Indicates No “Call for Heat” Flash Fast Startup-Flame sense calibration Heart Beat Normal operation Recycle - Flame failed during run Flame sensed out of sequence Flame sense leakage to ground Low secondary voltage supply - below 15.5 Vac) 6 + 2...
  • Page 58: Rf Standing Pilot Operating Instructions

    RF STANDING PILOT OPERATING INSTRUCTIONS Features • Self powered millivolt receiver/valve • Thermostat performance • Auto mode • Self powered millivolt control • Integrated Valve Electronics • Failure analysis • Pilotstat interlock • F or C temperature units Please review and retain the instructions included with the RF Transmitter. It provides additional information and details concerning the operational procedures and functions for the RF Remote Control.
  • Page 59: Rf Transmitter Functions

    RF TRANSMITTER FUNCTIONS FIRST USE OF TRANSMITTER Status Begin communication between transmitter and receiver/valve. Transmit unique code. Confirm recognition between transmitter and receiver/valve. Chose Remote or Local operation. Operation in the Remote Position AUTO Mode With the control in the AUTO mode, the flame in the main burner will turn on, off, or change height based on the heat needed to maintain the set temperature. Status Set to AUTO.
  • Page 60: Rf Wiring Diagram

    RF WIRING DIAGRAM WIRING DIAGRAM WITH BLOWER Figure 85 Page 60 21759-6-0608...
  • Page 61: Rf Standing Pilot Lighting Instructions

    RF STANDING PILOT LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE. A. This appliance has a pilot which must be lighted by hand.
  • Page 62: Maintenance And Service

    MAINTENANCE AND SERVICE Please Note It is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. It is not unusual for your gas fireplace to give off some odor the first time it is burned.
  • Page 63: Parts View

    PARTS VIEW 21759-6-0608 Page 63...
  • Page 64: Parts List

    INDEX PART NUMBER DVP42 R-7654 17426 R-7567 R-7573 17363 M170 17142 R-7575 17430 R-7574 17247 10554 17162 R-3492 17357 17445 17804 17381 17187 17190 17188 R-7612 R-7611 R-5747 R-5748 R-6116 R-6117 R-7617 11269 Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death. Page 64 PARTS LIST DVP48...
  • Page 65: Parts List

    INDEX PART NUMBER DVP42 P200 P203 P185 R-5676 11499 11377 17370 17368 17369 R-2423 R-1109 R-7577 R-7578 R-5745 R-5746 R-6114 R-6115 17161 17795 17796 16223 R-3435 R-5751 R-2708 R-3436 R-1995 R-5160 R-1616 R-721 18858 R-7731 R-7831 R-9035 R-9032 R-9033 R-9034 Use Only Manufacturer’s Replacement Parts.
  • Page 66: Fbb4 Optional Variable Speed Blower Installation

    FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION Attention: Install blower assembly before connecting gas inlet supply line Note: Junction box on right side of fireplace must be pre-wired at time of fireplace installation for use with blower assembly. It is recommended that an ON/OFF wall switch be installed that will activate the power supply to the furnace by a qualified electrician.
  • Page 67 FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION 21759-6-0608 FBB4 R7649 R4192 R4186 110 VOLT AC JUNCTION BOX B L O W E R A S S E M B LY COMPLETE FAN CONTROL SPEED CONTROL KNOB SPEED CONTROL Page 67...
  • Page 68: Junction Box Wiring Installation Instructions

    JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN POWER SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).
  • Page 69: Accessories

    The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62220-2623. Accessory Fan Kit Simulated Brick Panels...
  • Page 70: How To Order Repair Parts

    Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store. Shipments contingent upon strikes, fires and all causes beyond our control. Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-2623 Page 70...
  • Page 71: Service Notes

    SERVICE NOTES 21759-6-0608 Page 71...