Connect Control Wiring; Compressor Crankcase Heater; Airflow Selection For Variable Speed Furnaces (Non- -Communicating) - Carrier Infinity 24ANB7 Installation Instructions Manual

Infinity 2-stage air conditioner with puronr refrigerant 2-5 tons (sizes 24-60)
Hide thumbs Also See for Infinity 24ANB7:
Table of Contents

Advertisement

Connect Ground and Power Wires
Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 6.
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
FIELD POWER
WIRING
FIELD GROUND
WIRING
Fig. 6 - - Line Connections

Connect Control Wiring

This unit is capable of communication with an Infinity Control, or
will operate using standard 24v 2- -stage thermostat. Route 24- -v
control wires through control wiring grommet and connect leads to
control board.
When an Infinity User Interface is available,
connect to A and B connections only. If additional grounding is
needed, use C terminal. If a 2- -stage thermostat is used, connect to
the R, C, Y1, and Y2 connections. Refer to the wiring label to
further clarification.
Use No. 18 AWG color- -coded, insulated (35_C minimum) wire. If
thermostat is located more than 100 ft. (30.48 m) from unit, as
measured along the control voltage wires, use No. 16 AWG
color- -coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from
incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum.
NOTE:
Use of available 24v accessories may exceed the
minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections
to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to
outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than
80 ft. (24.38 m). Refer to the Application Guideline and Service
Manual
Longline
Section- -Residential
Conditioners and Heat Pumps.
Airflow Setup for Infinity Control Furnace or FE
Fan Coil (communicating)
When using an Infinity User Interface, airflow is automatically
selected based on equipment size. See User Interface Installation
Instructions and air conditioner Product Data for available
adjustments.
CONTACTOR
GROUND
LUG
A91056
Split- -System
Air
Airflow Selections (ECM Furnaces - - non commu-
nicating)
The ECM Furnaces provide blower operation to match the
capacities of the compressor during high and low stage cooling
operation. Tap selections on the furnace control board enable the
installing technician to select the proper airflows for each stage of
cooling. Below is a brief summary of the furnace airflow
configurations
1. The Y2 call for high stage cooling energizes the "Cool" tap
on the control board. The grey wire from cool tap is connec-
ted to tap 5 on the motor. Refer to the furnace Product Data
to find the corresponding airflow. If the airflow setting for
high cooling needs to be switched from tap 5 to a different
tap, jumper a connection from the cool tap to the desired tap
so that the Y2 signal is communicated via the cool tap to the
desired speed tap.
2. The Y1 call for low stage cooling energizes the "Fan" tap
on the control board. The red wire from the fan tap is con-
nected to tap 1 on the motor. Refer to the furnace Product
Data to find the corresponding airflow. If the airflow setting
for low cooling needs to be switched from tap 1 to a differ-
ent tap, jumper a connection from the Fan tap to the desired
tap so that the Y1 signal is communicated via the Fan tap to
the desired speed tap. The Y1 setting will also govern the
continuous fan airflow for the furnace.
Refer to the literature for the furnace and air conditioner Product
Data for further details.
Airflow Selection for Variable Speed Furnaces
(non- -communicating)
The variable speed furnaces provide blower operation to match the
capacities of the compressor during high and low stage cooling
operation. The furnace control board allows the installing
technician to select the proper airflows for each stage of cooling.
Below is a summary of required adjustments. See furnace
installation instructions for more details:
1. The A/C DIP switch setting determines airflow during high
stage cooling operation. Select the A/C DIP switch setting
corresponding to the available airflow shown in the furnace
Installation Instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data
for HIGH speed.
2. The CF DIP switch setting determines airflow during low
stage cooling operation. Select the CF DIP switch setting
corresponding to the available airflow shown in the furnace
installation instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data
for LOW speed. If a higher or lower continuous fan speed is
desired, the continuous fan speed can be changed using the
fan switch on the thermostat. Refer to the furnace Installa-
tion Instructions for details of how to use this feature.
Airflow Selection for FV4C Fan Coils (non- -com-
municating)
The FV4 provides high- - and low- -stage blower operation to match
the capacities of the compressor at high- - and low- -stage.
To select recommended airflow, refer to the FV4C Installation
Instructions. The FV4C utilizes an Easy Select control board that
allows the installing technician to select proper airflows. This fan
coil has an adjustable blower- -off delay factory set at 90 sec. for
high- - and low- -stage blower operation.
When using a communicating control with the fan coil or the
furnace, dip- -switch adjustments are not necessary. The outdoor
unit configuration and the indoor airflows are determined by
communicating control setup.
5

Advertisement

Table of Contents
loading

Table of Contents