Field Fabricate Ductwork; Unit Duct Connections - Bryant 580G Installation, Start-Up And Service Instructions Manual

Sizes 240-360 single package rooftop electric cooling/gas heating units
Table of Contents

Advertisement

MOTOR
UNIT
MOTOR
SHAFT
SHAFT
SIZE
HP
DIA.
SPEED
580G,H
(in.)
5
1.12
240
10
1.38
15
1.62
7.5
1.38
300
10
1.38
15
1.62
10
1.38
324
15
1.62
20
1.62
10
1.38
360
15
1.62
20
1.62
NOTE: Motor shaft speed is 1750 rpm. The fan shaft diameter is 1
A. Positioning
Provide clearance around and above unit for airflow, safety,
and service access (Fig. 2 and 3).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
For proper unit operation, adequate combustion and ventila-
tion air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas Code,
ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
III. FIELD FABRICATE DUCTWORK
Secure all ducts to building structure. Use flexible duct con-
nectors between unit and ducts as required. Insulate and weath-
erproof all external ductwork, joints, and roof openings with
counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
To attach ductwork to roof curb, insert ductwork approx-
imately 10 to 11 in. up into the curb. Connect ductwork to
14-gage roof curb material using sheet metal screws driven
from inside the duct.
WARNING: For vertical supply and return units, tools
or parts could drop into ductwork and cause an injury.
Install 90 degree elbow turns in the supply and return
ductwork between the unit and the conditioned space.
If a 90 degree elbow cannot be installed, then grilles of
sufficient strength and density should be installed to
prevent objects from falling into the conditioned space.
IV. UNIT DUCT CONNECTIONS
A. 580G Units
Unit is shipped for through-the-bottom duct connections. Duct-
work openings are shown in Fig. 2. Attach all ductwork to
roof curb. Air distribution is shown in Fig. 5. Refer to
installation instructions shipped with accessory roof curb for
more information.
Table 2 — Evaporator Fan Motor Data
MOTOR
FAN
SHEAVE
MOTOR
PITCH
SHEAVE
DIAMETER
(rpm)
(in.)
717
BK55
4.8
924
2BK50
4.4
1096
2B5V56
5.7
773
BK60H
5.4
962
1B5V60
6.1
1106
2B5V54
5.5
848
2BK50
4.4
1059
2B5V48
4.9
1187
2B5V58
5.9
884
2BK50
4.4
1096
2B5V56
5.7
1187
2B5V58
5.9
11
16
FAN
BUSHING
SHEAVE
FAN
DIAMETER
PITCH
SHEAVE
(in.)
DIAMETER
(in.)
None-1.125
1B5V124
12.4
None-1.375
2B5V86
8.6
B-1.625
2B5V90
9.1
H-1.375
1B5V124
12.4
H-1.375
1B5V110
11.1
B-1.625
2B5V86
8.7
None-1.375
2B5V94
9.4
B-1.625
2B5V80
8.1
B-1.625
2B5V86
8.7
H-1.375
2B5V90
9.0
B-1.625
2B5V90
9.1
B-1.625
2B5V86
8.7
inches.
B. 580H Units
Remove shipping covers from supply and return air open-
ings. Attach field-supplied ductwork to unit. Use a single duct
over both return openings and a single duct over both sup-
ply openings. See Fig. 3 for duct opening dimensions. Secure
all ducts to the building structure. See Fig. 6. Use flexible
duct connectors between unit and ducts as required.
Install accessory barometric relief or power exhaust in
the field-fabricated return ductwork. Refer to Power
Exhaust/Barometric Relief Damper Hood section for more
information.
Fig. 5 — Air Distribution — Thru-the-Bottom
Fig. 6 — Air Distribution — Thru-the-Side
—7—
BUSHING
OUTSIDE
BELT
DIAMETER
BELT
(QUANTITY)
(in.)
LENGTH
B-1.9375
BX59
62
B-1.9375
(2) BX51
54
B-1.9375
(2) 5VX530
53
B-1.9375
BX59
62
B-1.9375
5VX590
59
B-1.9375
(2) 5VX530
53
B-1.9375
(2) BX52
55
B-1.9375
(2) 5VX500
50
B-1.9375
(2) 5VX530
53
B-1.9375
(2) BX51
54
B-1.9375
(2) 5VX530
53
B-1.9375
(2) 5VX530
53
BELT
TENSION
(lb at
.24 in.)
5.10
5.21
6.00
6.48
7.37
6.12
5.27
6.63
7.31
5.24
6.00
7.31