Bradford White M1TW40S Series Service Manual page 11

Ttw series through-the-wall gas water heaters
Table of Contents

Advertisement

Steady state operation.
7
During Steady State Operation the Control Monitors:
Thermostat temperature sensor- When set point temperature is satisfied, gas valve is shut down and
blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status
code.
Pressure switch / Blower temperature switch- If either switch opens, pilot valve and main valve is shut
down. The blower continues to runs for 30 seconds attempting to close the circuit. The control LED Flashes
3 times with 3 second pause.
Flame Sensor- If flame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts
to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control
re-attempts to light pilot starting at normal heating sequence #2.
Thermostat satisfies
8
Burner off.
9
Blower post purge (15 seconds).
10
1. Flammable Vapor Sensor Fault:
a) If the resistance is greater than 70,000 Ohms - the gas control immediately turns off all outputs. Control waits
and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the
gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times then once with a three second
pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to
flammable vapor lockout.
b) If the resistance is below 3000 ohms - The gas control immediately turns off all outputs and proceeds to flash
8 times then once with three second pause. The error self clears if the resistance returns to normal range for at
least 15 seconds.
2. Temperature Sensor Fault:
a) Temperature sensor detected open circuit - The gas control Immediately turns off all outputs and proceeds to
flash 8 times then three times with three second pause. The error self clears if the fault clears for at least 15 seconds.
b) Thermal well sensors not reading the same temperature within ±5.5 °F - The gas control Immediately turns off
all outputs and proceeds to flash 8 times then three times with three second pause. The error self clears if the fault
clears for at least 15 seconds.
c) Water temperature in excess of TCO (Temperature Cut Off) limit - The gas control immediately turns off pilot
main valve and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset.
To reset control, rotate knob of temperature control to the minimum setting for at least 6 seconds before returning
to desired temperature setting.
(Control LED flashing once every 4 seconds).
Sequence of Operation
Page 11
Page 11
11