Wiring - Main Power; Wiring - Low Voltage Wiring; Figure 10 Common Wall Mounting Installations; Figure 11 Unit 24V Terminal Board - Bard CH4S1 Installation Instructions Manual

Wall mounted package heat pumps
Table of Contents

Advertisement

FIGure 10
cOmmOn Wall mOuntInG InstallatIOns
Closet Installation
Note: duct maybe in attic or
below rafters as shown.
Unit (outside)
Supply Air
WIrInG – maIn POWer
Refer to the unit rating plate for wire sizing information
and maximum fuse or "HACR" type circuit breaker
size. Each outdoor unit is marked with a "Minimum
Circuit Ampacity". This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required. If this is the
case, the unit serial plate will so indicate. All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked "Use Copper
Conductors Only". These instructions must be adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a "Maximum Time Delay
Relay Fuse" or "HACR" type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.
See "Start Up" section for important information on
three phase scroll compressor start ups.
Rafters
Duct
Finished Ceiling
Grille
Wall Sleeve
Grille
Raised Closet Floor
Return Air
MIS-2240
WIRING – LOW VOLTAGE WIRING
230 / 208V, 1 phase and 3 phase equipment have 24V
transformers with dual primary voltage. All equipment
leaves the factory wired on 240V tap. For 208V
operation, reconnect from 240V to 208V tap. The
acceptable operating voltage range for the 240 and 208V
taps are:
taP
240
208
NOTE: 460V units require no action. The voltage
should be measured at the field power
connection point in the unit and while the unit is
operating at full load (maximum amperage
operating condition).
FIGure 11
unIt 24V thermOstat cOnnectIOns
OPTIONAL
8403-061
OUTDOOR
C
G
Rc
Rh
SENSOR
GND
OD
GND
ID
C
G
R
OPTIONAL
C
G
R
8403-062
INDOOR
SENSOR
Factory Jumper
 Only needed if dehumidification is used.
Eleven (11) wires should be run from thermostat
subbase to the 24V terminal board in the unit. An
eleven conductor, 18 gauge copper color-coded
thermostat cable is recommended. The connection
points are shown in Figure 11. An additional wire is
needed if dehumidification is used.
ImPOrtant
Only the thermostat combinations as shown
above will work with this equipment.
table 3
thermOstat WIre sIZe
transformer
Fla
Va
65
2.3
ranGe
253 – 216
220 – 187
THERMOSTAT BARD PART
#8403-052, 8403-053, 8403-055
Y1
Y2
B
W1
THERMOSTAT
BARD PART #8403-060
W1/E
Y1
Y2
D/YO
O/B
W2
L
Y
Y1
B
W1
W2
W3
E
L
DH
UNIT LOW VOLTAGE
TERMINAL BLOCK
maximum
Wire Gauge
Distance
In Feet
20 gauge
45
18 gauge
60
16 gauge
100
14 gauge
160
12 gauge
250
Manual 2100-455M
Page
15 of 28
AUX
A
1
O1
MIS-2026 C