Unconfined Space; Confined Space; Exhaust Fans; Louvers And Grilles - American Water Heater BCG3 Instruction Manual

Low nox series 108 commercial gas water heaters installation, operation, service, maintenance, limited warranty
Table of Contents

Advertisement

Never obstruct the flow of ventilation air. if you have any doubts
or questions at all, call your gas supplier. failure to provide the
proper amount of combustion air can result in a fire or explosion
and cause property damage, serious bodily injury or death.

unconfined space

An unconfined Space is one whose volume iS NoT LeSS THAN
50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the
total input rating of all appliances installed in the space. Rooms
communicating directly with the space, in which the appliances
are installed, through openings not furnished with doors, are
considered a part of the unconfined space.
Makeup air requirements for the operation of exhaust fans,
kitchen ventilation systems, clothes dryers and fireplaces shall
also be considered in determining the adequacy of a space to
provide combustion, ventilation and dilution air.
unusually tight construction
in unconfined spaces in buildings, infiltration may be adequate to
provide air for combustion, ventilation and dilution of flue gases.
However, in buildings of unusually tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.)
additional air must be provided using the methods described in
the Confined Space section that follows.

confined space

A Confined Space is one whose volume iS LeSS THAN 50 cubic
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input
rating of all appliances installed in the space.

Venting

THe iNSTRuCTioNS iN THiS SeCTioN oN VeNTiNG muST
Be foLLoWeD To AVoiD CHoKeD ComBuSTioN oR
ReCiRCuLATioN of fLue GASeS. SuCH CoNDiTioNS
CAuSe SooTiNG oR RiSKS of fiRe AND ASPHYXiATioN.
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will
retard a free draft.
Type B venting is recommended with these heaters. for typical
venting application see TeCHNiCAL DATA VeNTiNG on pages
17 and 18.
This water heater must be vented in compliance with all local
codes, the current revision of the National fuel Gas Code (ANSi-
Z223.1) and with the Category i Venting Tables.
if any part of the vent system are exposed to ambient temperatures
below 40°f it must be insulated to prevent condensation.
openings must be installed to provide fresh air for combustion,
ventilation and dilution in confined spaces. The required size for
the openings is dependent on the method used to provide fresh
air to the confined space AND the total Btu/hr input rating of all
appliances installed in the space.

exhaust fans

Where exhaust fans are installed, additional air shall be provided
to replace the exhausted air. When an exhaust fan is installed
in the same space with a water heater, sufficient openings to
provide fresh air must be provided that accommodate the
requirements for all appliances in the room and the exhaust fan.
undersized openings will cause air to be drawn into the room
through the water heater's vent system causing poor combustion.
Sooting, serious damage to the water heater and the risk of fire
or explosion may result. it can also create a risk of asphyxiation.

louVers and grilles

The free areas of the fresh air openings in the instructions that
follow do not take in to account the presence of louvers, grilles or
screens in the openings.
The required size of openings for combustion, ventilation and
dilution air shall be based on the "net free area" of each opening.
Where the free area through a design of louver or grille or screen
is known, it shall be used in calculating the size of opening
required to provide the free area specified. Where the louver and
grille design and free area are not known, it shall be assumed
that wood louvers will have 25% free area and metal louvers and
grilles will have 75% free area. Non motorized louvers and grilles
shall be fixed in the open position.

Venting installation

• Do not connect the heater to a common vent or chimney with
• Where a separate vent connection is not available and the vent
15
solid fuel burning equipment. This practice is prohibited by
many local building codes as is the practice of venting gas
fired equipment to the duct work of ventilation systems.
figure 11.
pipe from the heater must be connected to a common vent with
an oil burning furnace, the vent pipe should enter the smaller
common vent or chimney at a point above the large vent pipe.
figure 12.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Abcg3Low nox 108 series

Table of Contents