Rack Configurations For Distributing Power To Hp Proliant Dl Servers - HP ProLiant DL140 - G2 Server Introduction Manual

Critical factors in intra-rack power distribution planning for high-density systems
Hide thumbs Also See for ProLiant DL140 - G2 Server:
Table of Contents

Advertisement

Rack configurations for distributing power to HP ProLiant DL servers

This section describes power distribution configurations for a high-density server system based on HP
ProLiant DL 360 G5 servers. The ProLiant DL 360 G5 is a 1U server that uses an auto-ranging power
supply and supports power redundancy when used in the 1 + 1 power supply configuration option.
These configurations use monitored PDUs and fixed cord extension bars (Figure 8).
Figure 8. HP ProLiant
DL360 G5 system and power distribution components
HP ProLiant DL360 G5 server
Table 3 shows the difference in power requirements of the ProLiant DL360 G5 server when it is used
in two different scenarios. In one scenario, the server is configured and utilized to about half its
potential. In the other scenario, the server is nearly at maximum configuration and estimated to run at
a relatively high (70 percent) state of use. Both configurations employ redundant power (two supplies
per system) and use high-line voltage. The maximum configuration operates off three-phase power.
Although a standard 42U rack can physically accommodate 42 ProLiant DL360 G5 servers, it is
advisable to leave space for server expansion, power distribution components such as PDUs and
UPSs, keyboard/video/mouse (KVM) equipment, and/or networking components.
Table 3. HP ProLiant DL360 G5 server power distribution configurations
No. of
servers
System configuration
in rack
(each server)
30
One 2.0-GHz processor,
2 GB memory, one PCI-E
card, two 36 GB hard
drives, system utilization
estimated at 40%
30
Two 3.0-GHz
processors, 16 GB
memory, two PCI-E
cards, four 146-GB SAS
hard drives, system
utilization estimated at
70%
Products and part numbers discussed in this document are subject to change without notice. Refer to
the URL provided in the "For more information" section for the latest available products and part
numbers
Total VA and current requirements were determined using the HP Power Calculator Utility available at
the following URL:
http://h30099.www3.hp.com/configurator/calc/Power%20Calculator%20Catalog.xls
Monitored PDU
Total
No./type
Total VA
current
of outlets
required
draw
required
8.5 kVA
36 A
60/C13
14.5 kVA
60 A
60/C13
Fixed cord
Extension Bar
Recommended PDU
1Ф 208VAC:
Monitored PDU AF506A (x2)
or monitored PDU AF505A
1Ф 220VAC:
Monitored PDU AF508A (x2)
3Ф 208VAC:
Monitored PDU AF916A
and
fixed cord extension bar
351655-B21 (x5)
3Ф 220VAC:
Monitored PDU AF509A (x2)
12

Advertisement

Table of Contents
loading

Table of Contents